Loading...
HomeMy WebLinkAbout272062_1_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101105790 PROJECT ADDRESS: 501 S Santa Fe St PLAN CHECK ENGINEER: So, AnsonTEL:714 647-5830 EMAIL: aso@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B, SPK OCCUPANCY CLASSIFICATION(S): B, S-2 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 2/2/2021 INITIAL REVIEW 2/13/2021 EXPIRATION 8/1/2021 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Ali Olfati 3. TEL: (562)986-4313 FAX: (562)986-4312 VALUATION: $60,000.00 EMAIL: olfatidesign@aol.com FLOOD ZONE: X-0602320276J APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5830 for an appointment.Sheet A-1Under Proposed Work, add proposed trash enclosure.Under Prevailing Codes, delete note k and revise it to City of Santa Ana Municipal Code.Show accessible route from the rear-exterior door to the trash enclosure.Show an egress route from the rear-exterior door to Santa Fe Street. Show the existing gate at the driveway, and provide an egress door at the gate.Specify a van accessible parking space on the site plan.Remove truncated domes at the access aisle.Revise the scale to 3/32” = 1’-0”.Sheet A1-2Code sections are outdated. Use the 2019 version of California Building Code.Sheet A-5Provide an egress door at door #11.Label the use of space in the middle of the building.Specify the travel distances on the plan.Sheet A-10Trash enclosure plan indicates wall height of five feet. However, detail 4 and 5 shows 6-foot tall wall. Verify discrepancy.Sheet S-3Revise the crossed reference detail number to “1/S5”.Structural CalculationsAt grid line A between grid line 2 and 3, a 12-foot wide by 14-foot tall concrete wall is being removed. A beam and columns calculations have been provided for the design of HSS7x5x1/2 for the gravity load. Provide out-of-plane calculations for the columns, anchor connections, and top and bottom end-connection design. The top of HSS tube determinates below the opening. Provide calculations for load transfer to the roof diaphragm.