HomeMy WebLinkAbout271686_2_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101105688
PROJECT ADDRESS:
3431 W Carriage Dr
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
III B
OCCUPANCY CLASSIFICATION(S):
F-1
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
1/20/2021
INITIAL REVIEW
1/29/2021
EXPIRATION
7/19/2021
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Jonathan L Zane
3.
TEL:
(909)376-7138
FAX:
(909)825-7624
VALUATION:
EMAIL:
jlzane@roadrunner.com
FLOOD ZONE: X-0602320258J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
- Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700).
-Public Works Agency approval (647-5039).
Sheet C-1.0:
For clarity, please provide operation information for the cannabis facility.
Please provide water tank and C02 tank dimensions and capacity (diameters, heights, gallon, weight with and whiteout contents etc.) on the plan.
Please show dimensions of concrete pads on the plan – drawn to scale.
Sheet A-1.0:
Title Block: Please update applicable codes and module codes to the current code edition.
Please provide tanks specification and cut-sheets on the plan.
Water tank: 4 anchor bolts appeared insufficient. Please coordinate with structural calculation and revise plan accordingly.
Water tank anchorage detail: Please specify minimum embedment of the anchor bolts.
Structural Calculation:
Storage tanks: Please provide lateral calculations when tanks are empty.
Provide anchorage calculation in concrete in accordance with Chapter 17 of ACI 318.
Foundation and attached element shall design with impulsive and convective (sloshing) effects. (ASCE7-16, Section 15.7.6.1)
Seismic design: Please use R factor of 3.0
Please revise plans and details as necessary.