HomeMy WebLinkAbout262290_3_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
102102848
PROJECT ADDRESS:
2319 W Russell Ave
PLAN CHECK ENGINEER:
Lee, WayneTEL:714
647-5848
EMAIL:
wlee@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3, U
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
2/5/2020
INITIAL REVIEW
3/26/2020
EXPIRATION
4/1/2021
RECHECKS:
1.1/12/2020
PROJECT APPLICANT CONTACT PERSON:
2.2/26/2021
Carlos Tobias
3.
TEL:
(714)727-4982
FAX:
VALUATION: $50,000.00
EMAIL:
tobyc2525@gmail.com
FLOOD ZONE: X-0602320257J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
-Public Works Agency approval (647-5039).
- School District Compliance Certificate; and a copy of the building permit application, signed by
the plan check engineer, shall be required by the School District to verify the scope of the work.
PLAN CHECK COMMENTSPlease fill out part 1 (project information) of the school fee application form and return with next submittal package. A copy of the form is attached with this correction letter and also in the plan check notice email.The architectural designer or architect shall sign ALLarchitectural plans.
Sheet A1.1. Show 30-inch clear width for water closet compartments and 24-inch clearance in front of a water closet. (plan shows 36”x24” around the water closet is not correct)
Sheet A1.4. Specify ICC approval number: ESR-1475(not AC-438)forasphalt shingle roof coverings on plan.
Sheet A1.4. Callout attic vent locations, sizes and types on plans. (CRC R806.2)
STRUCTURAL
Provide vertical support for the 6X12 ceiling beam AND provide positive connection detail. Trace the force to footing.
Sheet S-2. Provide structural design and details for the hips and their support located at the masterbedroom addition.
Please note that the plan review expiration date is 4/1/2021. Revised plans shall be and obtain approval prior to the expiration date. This plan check may not be extended.
No corrections on the structural calculation.
END OF COMMENTS