Loading...
HomeMy WebLinkAbout270300_4_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101105259 PROJECT ADDRESS: 1554 W Washington Ave PLAN CHECK ENGINEER: Ahangian, KathyTEL:714 647-5812 EMAIL: Kahangian@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): R-3 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 11/20/2020 INITIAL REVIEW 12/7/2020 EXPIRATION 5/19/2021 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Ed Yandoc 3. TEL: (714)745-9987 FAX: VALUATION: $5,400.00 EMAIL: edyandoc@gmail.com FLOOD ZONE: X-0602320144J Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5812 for an appointment. Please see corrections on submitted plans. Red marked set must be returned with revised plans. Plans resubmitted without the red markup set may result in delayed review time and additional plancheck fees. This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information. SPDWS in effect is 2015, SPDWS 2008 is an old version, please revise data accordingly. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: -Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. - Proof of Worker's Compensation Insurance shall be required at the time of permit issuance. Delete notes and details that do not apply to this project. Remove Hardy frame detail if it is not applicable. Provide a fully dimensioned Site Plan on the drawings and on a separate 8-1/2" x 11" sheet of paper. Existing house is 1245 sf, New addition is 498, New garage is 441sf, please revise numbers on cover sheet and see planning for approval. Provide eave / overhang / projection setback to all property lines. On east side the wall is jogged, top plate cannot be the same, there would a height difference , please revise accordingly and see planning. Please revisit elevations to match floor plan.Projections of dwelling units and accessory buildings without an automatic residential fire sprinkler protection are not permitted less than 2 feet to the property line and are required to be 1 hour fire rated on the underside with a fire separation distance between 2 feet and 5 feet. (CRC Table R302.1 (1)) Walls of dwelling units and accessory buildings without an automatic residential fire sprinkler protection with a fire separation distance less than 5 feet are required to have a full one hour rating. (CRC Table R302.1 (1)) Show location of heating equipment on the plans. (CRC R303.8) Provide a minimum of two No. 4 bars at top and at bottom of continuous footing. Provide complete roof framing plan for entire roof. Provide support for all hip beam/ ridge board connections. Provide shearwall on east side (or line 1). Sleepers cannot act as beam, please provide hip beam.Insulation shown on the plans does not agree with CF-1R form; revise framing plans. Wall R= 15.