HomeMy WebLinkAbout271288_2_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101105567
PROJECT ADDRESS:
2114 1/2 N Candis Ave
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3, U
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
1/5/2021
INITIAL REVIEW
2/4/2021
EXPIRATION
7/4/2021
RECHECKS:
1.4/19/2021
PROJECT APPLICANT CONTACT PERSON:
2.
Anh Phan
3.
TEL:
(714)487-7926
FAX:
VALUATION: $50,000.00
EMAIL:
VICTORPH.DESIGN@GMAIL.COM
FLOOD ZONE: X-0602320144J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
-Police Department approval on the corrected/final set of drawings (647-5840).
-Public Works Agency approval (647-5039).
- Proof of Worker's Compensation Insurance shall be required at the time of permit issuance.
- School District Compliance Certificate; and a copy of the building permit application, signed by
the plan check engineer, shall be required by the School District to verify the scope of the work.
-Grading Permit. Application is made through the Building Safety Division (647-5800) and the
plan review is by the Public Works Agency (647-5039).
Sheet A1:
Reminder: Please revise job address using half address for the proposed ADU. Apply to all sheets.
Sheet A2:
Wall located less than 5-ft from the property line shall be constructed with a one-hour fire-rated assembly. Please show one-hour wall and provide detail of one-hour wall assembly.
2nd Review Comment: Referenced detail 11/AD1 – Please revise detail to specify 7/8” thick stucco on the exterior side of wall.
Structural Review Comment:
Structural framings may be change due to the architectural revisions per comments above. Structural plan review will continue at time of resubmittal. Additional comments may be required.
2nd Review Comment: 2x6 wall studs are required for wall height more than 10-ft. Please revise sheet S1 to show 2x6 wall with 6x headers.