HomeMy WebLinkAbout270484_2_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101105323
PROJECT ADDRESS:
329 1/2 E Pine St
PLAN CHECK ENGINEER:
Lee, WayneTEL:714
647-5848
EMAIL:
wlee@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
11/30/2020
INITIAL REVIEW
12/21/2020
EXPIRATION
5/29/2021
RECHECKS:
1.04/26/2021
PROJECT APPLICANT CONTACT PERSON:
2.
Rafael Estevez
3.
TEL:
(323)516-5846
FAX:
VALUATION: $35,000.00
EMAIL:
carlos@arkitpp.com
FLOOD ZONE: X-0602320276J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.
This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
- Public Works Agency approval (647-5039).
PLAN CHECK COMMENTS:
Show the location of the address number on the site plan. The address number shall be legible and placed in a position that is visible from the street or road fronting the property.
Provide footing detail at the new wall to enclose the garage door opening. Maintain 8 inches from bottom of the wood sill plate to exterior finish grade. A new concrete curb may be needed.
Sheet A.3. Cross-reference section A-A to the floor plan.
Sheet A.3. Show smoke alarms in each sleeping room and vicinity area outside each bedroom and at each level on the floor plan. [2019 CRC R314].
Sheet A.3. Show carbon monoxide alarms outside all sleeping rooms and at each level on the floor plan. [2019 CRC R315].
Sheet A.3. Clarify in detail 18/A3. It appears not possible to install new vapor barrier under the existing slab. For garage conversion to a bedroom, please show method of sealing the existing slab. Please specify applicable method to seal the existing concrete slab.
Sheet A.3. Remove the note on the existing window: “to be demo”. Are you altering windows?
STRCUTRUAL
Sheet A3. Detail #4 for interior partition does not apply to this project. There is no T-bar ceiling and diagonal bracing does not apply. Provide a section or details showing the top and bottom anchorage for the interior non-bearing partitions. Show details for both perpendicular and parallel to ceiling or floor joists condition.