HomeMy WebLinkAbout275289_1_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101106732 PROJECT ADDRESS: 2625 W St Gertrude Pl PLAN CHECK ENGINEER: Lee, WayneTEL:714 647-5848 EMAIL: wlee@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): R-3, U PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 5/20/2021 INITIAL REVIEW 5/23/2021 EXPIRATION 11/16/2021 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Ricardo Carballea 3. TEL: (714)351-4847 FAX: VALUATION: $60,000.00 EMAIL: ricarballea82@yahoo.com FLOOD ZONE: X-0602320257J Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.California Building Standards Code with local amendments and to clearly indicate the scope of work under this building permit application. There may be additional requirements when complete construction drawings and supporting data is submitted for Building Safety Division review. This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: -Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. -Public Works Agency approval (647-5039). - School District Compliance Certificate; and a copy of the building permit application, signed by the plan check engineer, shall be required by the School District to verify the scope of the work. PLAN CHECK COMMENTS: ARCHITECTURAL Sheet 01. Add 2019 California Green Building Standards Code (CALGreen) to the governing Codes. The addition portion is required to comply with 2019 California Green Building Standards Code mandatory requirements. Show compliance on the plan. Sheet 02. Revise plans to indicate that a landing, with a width not less than the width of door and length in the direction of travel of not less than 36 inches, will be provided on each side of doors. The elevation of landing shall not exceed 1 ½ inch difference than the threshold of the doorway (7 3/4 inch if door does not swing over the landing or steps) in each direction. Revise plans at door from the door #01 to show compliance. (CRC R311.3.1) Sheet 02. The water heating system is altered per energy design. Show location of the new tankless water heater on the floor plan. Sheet 01. The cooling system is altered per energy design. Show location of the new packaged AC unit on the site plan. Sheet T1. CF1R form. Update the two west-facing windows as new in the fenestration design (page 4). See floor plan for window alteration for type 1 window. STRUCTURAL Sheet 03. Construction Documents (1603): The design loads and other information pertinent to the structural design required by Sections 1603.1.1 through 1603.1.9 shall be indicated on the plans. Sheet SD1. Detail 4 and detail 6. Provide 8-16d at the roof/ceiling connection. (CBC Table 2308.7.3.1) Sheet SD1. Detail 8. Revise the spacing of the new “ST18” strap to match the spacing of the ceiling and roof rafters to form a continuous roof tie. No red marks on the drawings and the structural calculation. END OF COMMENTS