Loading...
HomeMy WebLinkAbout273815_2_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101106296 PROJECT ADDRESS: 3400 W Warner Ave Unit# A PLAN CHECK ENGINEER: Lee, WayneTEL:714 647-5848 EMAIL: wlee@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: III B, SPK OCCUPANCY CLASSIFICATION(S): A-3, B, M, S-1 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 3/30/2021 INITIAL REVIEW 4/14/2021 EXPIRATION 9/26/2021 RECHECKS: 1.06/01/2021 PROJECT APPLICANT CONTACT PERSON: 2. Tatev Oganyan 3. TEL: (818)237-7867 FAX: VALUATION: EMAIL: tatev@theoganyanagency.com FLOOD ZONE: X-0602320258J Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used. Please see corrections on submitted plans. Red marked set must be returned with revised plans. Plans resubmitted without the red markup set may result in delayed review time and additional plancheck fees. This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: -Planning Division approval on the corrected/final set of drawings (714) 647-5804. Previously approved plans should be submitted to expedite the process. - Fire Department approval on the corrected/final set of drawings (714) 647-5839 or 647-5700. -Police Department approval on the corrected/final set of drawings (714) 647-5840. -Public Works Agency approval (714) 647-5039. -Orange County Sanitation District (714) 593-5756.PLAN CHECK COMMENTS This building is classified as Type VB.Regarding to this correction, Mr. James Taylor has updated the building analysis on the previous permit application. Please contact him for the information and update this submittal accordingly. On the cover sheet under code analysis area: Revise building analysis for the applicable area analysis method. Non-separation mixed used is incorrect. The occupancy group is incorrect. It should be B, M, S1, and A3. Revise building area calculation. (recommended in table format) Provide the floor plan showing area justification, the square footage, occupancy and calculation showing compliance with CBC Section 508.2 per James’s building analysis. Sheet A-1.5.0. Egress plan. EXIT #4. The existing exterior exit doors require 34” clearance per egress plan at door #101. The occupant load requires 161 at this door and this door is 36” in width. I am not sure if the 36” wide door can provide 34” clearance when fully open. Please verify and clarify the egress design and the door capacity on plan. You may email me the updated plans for review prior to printing the drawings. Please contact me if there are any questions regarding to this review. Thanks. END OF COMMENTS