HomeMy WebLinkAbout269354_3_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101104971
PROJECT ADDRESS:
1325 1/2 N Custer St
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
10/15/2020
INITIAL REVIEW
11/5/2020
EXPIRATION
4/13/2021
RECHECKS:
1.6/3/2021
PROJECT APPLICANT CONTACT PERSON:
2.6/22/2021
Catie Vuong
3.
TEL:
(714)260-4994
FAX:
VALUATION: $120,000.00
EMAIL:
catievuong@gmail.com
FLOOD ZONE: X-0602320163J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.General and Approval RequirementAll items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
-Police Department approval on the corrected/final set of drawings (647-5840).
-Public Works Agency approval (647-5039).
- School District Compliance Certificate; and a copy of the building permit application, signed by
the plan check engineer, shall be required by the School District to verify the scope of the work.
-Grading Permit. Application is made through the Building Safety Division (647-5800) and the
plan review is by the Public Works Agency (647-5039).
Sheet A0.1:
Exterior wall located within 5-ft of the fire separation distance shall be protected with one-hour fire-rated wall. Please specify one-hour wall on plan, and provide construction detail of one-hour wall assembly. Clearly cross-reference detail onto the plan.
2nd Review Comment: Response was incomplete. Please revise floor plan to show one-hour fire-rated wall and provide construction detail for one-hour fire-rated wall assembly.
3rd Review Comment: Keynote #15 referenced to detail 05/SD.1 for rated wall construction was not applicable. Please coordinate and revise detail reference accordingly.
Also, revise detal 09/SD.1 and 10/SD.1 to show/specify one (1) layer of 5/8” type ‘X’ gypsum board on the inside of wall.