PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101107107
PROJECT ADDRESS:
1900 E Warner Ave Unit# A
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B, SPK
OCCUPANCY CLASSIFICATION(S):
B, M
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
7/7/2021
INITIAL REVIEW
9/2/2021
EXPIRATION
1/3/2022
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Joshua Brecht
3.
TEL:
(951)691-7756
FAX:
VALUATION: $12,000.00
EMAIL:
adele@dmarchitect.net
FLOOD ZONE: X-0602320279J
APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Fire Department approval on the corrected/final sets of drawings ((714)573-6100)
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)Sheet C: Please Provide the following notes on the plan: Every Cannabis Business shall implement adequate ventilation system and odor control filtration measures to prevent odors from inside the cannabis facility from being detected outside the cannabis facility, to include building and the unit. A licensed Mechanical engineer shall design the system that is capable of preventing odors from inside the cannabis facility from being detected outside the cannabis facility.Mechanical, electrical and plumbing are not part of this plan review and approval. Square Footage: Please specify the total square footage of the existing building (the overall square foot of the existing building). Reminder: Plan shall be required to submit to Fire Department (OCFA) for plan review and approval prior to Building Plan review approval. Sheet A-1: On the plan, please show an accessible route from the public sidewalk and from the accessible parking stalls to the building primary entrance. Show detectable warning where it’s required. Please provide details for accessible parking stalls to show compliance with Section 11B-502, including marking and signage. Existing ramps: Please provide details to show ramps in compliance with Section 11B-405, including handrails. New loading and loading ramp: Please provide detail for loading and loading ramp. Ramp shall comply with Section 11B-405. Sheet A-2.1: Please show demolition information on the existing floor plan, where walls and storefront to be removed. Sheet A-2.2: Please provide a complete floor plan. Partial floor plan is insufficient. For clarity, please show demo information on the exiting floor plan. Existing storefront to be replace – Please clearly show how much of the existing storefront would be removed and replaced. New exterior door: Please show/provide tempered glass for glazing locate within 24” of door. On the plan, please clearly show the demising walls to separate suite A and B. the demising wall shall be a full-height wall (from slab to roof sheathing). Provide construction details and wall section. Please provide enlarged restroom plans to show restrooms in compliance with accessibility requirement per Chapter 11B, Division 6. All single accommodated restrooms shall be identified and all-gender restroom with the door symbol below: On the plan, please show/provide door landing and maneuver spaces on both sides of door for exterior and interior doors. Provide the notes on plane: Egress doors/gates shall be readily openable from the egress ide without the use of a key or special knowledge or effort. (1010.1.9)Openable parts of such hardware shall be 34 inches minimum and 44 inches maximum above the finish floor or ground. The force for pushing or pulling open a door shall be 5-lb maximum. Operable parts shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist. Egress Plan / Exit Plan: On the plan, please provide egress plan showing occupant load calculation for each area based on the use of each room, and show means of egress. Provide equipment and furniture on the plan. Show/provide illuminated exit signs and tactile exit signs at exit doorways. Indicate on plan, a readily visible durable sign posted on the egress side on or adjacent to the main exit door stating: “THIS DOOR TO REMAIN UNLOCKED WHEN THIS SPACE IS OCCUPIED”, is required. (1010.1.9.4)