Loading...
HomeMy WebLinkAbout276817_1_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101107164 & 101107165 PROJECT ADDRESS: 2008 S Yale St Unit# E & F PLAN CHECK ENGINEER: Lee, WayneTEL:714 647-5848 EMAIL: wlee@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: III B OCCUPANCY CLASSIFICATION(S): B, S-1 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 7/7/2021 INITIAL REVIEW 7/24/2021 EXPIRATION 1/3/2022 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Bryan Montoya 3. TEL: (949)251-1710 FAX: (949)225-1400 VALUATION: $80,000.00 / $40,000.00 EMAIL: bryan@cadtronics.net FLOOD ZONE: X-0602320256J APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Please return marked up set of drawings with corrections.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Police Department approval on the corrected/final set of drawings (647-5840) - Public Works Agency approval (647-5039)List all deferred submittals on cover sheet.List all separate permit items on the cover sheet.Sheet A2. Show overall length and width on plan for unit E and unit F.Sheet A2. Add note to tenant separation wall between unit E and unit F to specify ___-hours of fire-rating. Provide additional fire-assembly wall detail either test approved or per CBC prescribed detail if it is not 0-hour rated.Sheet A2 and detail 5/D1. Provide method of attaching partition walls to the roof.Do not support top of walls to other non-full height walls (As detail 9/D1) unless calculations and drawing prepared by a registered engineer are submitted for review. Submit structural engineering calculations.Sheet A2.Detail 9/D1 does not apply to the following location: Exterior full height wall and interior full height wall (6/D1). Sheet A4. Specify ICC approval number for TPO roofing-carlisle syntec system roof coverings.EGRESSSheet A3. Electrical legend. Update the compliance code to 2019 version.Sheet A3. Note the following on the plans: “The means of egress, including the exit discharge, will be illuminated to a level of not less than one foot-candle at the walking surface at all times the building space served by the means of egress is occupied”.Sheet A3.Note on the plans: “Exit signs shall be internally or externally illuminated at all times and shall be connected to an emergency power system (batteries, unit equipment or an on-site generator) that will automatically illuminate the exit signs for a duration of not less than 90 minutes.”Sheet A3.Provide and show tactile exit signs complying with Section 11B-703 and in accordance with Section 1013.4 at the exit sign. Each grade-level exterior exit door shall be identified by a tactile exit with the word “EXIT.”ENERGYProvide cool roofing as required by 2019 Energy Standards.The corrected/final ARCHITECTURAL drawings shall have the required energy efficiency compliance documentation with completed signature blocks filed on the plans.Show CRRC # for TPO roofing-carlisle syntec system. STRUCTURALUpdate the project address to “2008 S Yale Street unit E and unit F, Santa Ana” on the title block on each structural drawings and the cover sheet of the structural calculation.Sheet S2.01. Provide calculation to justify the 5.125”x15” GLB with 23 feet span on grid line 6 between grid line D and E.Sheet S3.01. Detail 5. Specify minimum 0.5” thickness base plate per structural calculation.END OF COMMENTS