HomeMy WebLinkAbout272728_3_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101105958
PROJECT ADDRESS:
401 W First St
PLAN CHECK ENGINEER:
Lee, WayneTEL:714
647-5848
EMAIL:
wlee@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B, SPK
OCCUPANCY CLASSIFICATION(S):
R-2
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
2/24/2021
INITIAL REVIEW
3/14/2021
EXPIRATION
8/23/2021
RECHECKS:
1.06/13/2021
PROJECT APPLICANT CONTACT PERSON:
2.
Scott Sullivan
3.
TEL:
(323)309-0445
FAX:
VALUATION: $75,000.00
EMAIL:
scott@relativityarchitects.com
FLOOD ZONE: X-0602320276J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.
This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
- Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700).
-Police Department approval on the corrected/final set of drawings (647-5840).
-Public Works Agency approval (647-5039).
- School District Compliance Certificate; and a copy of the building permit application, signed by
the plan check engineer, shall be required by the School District to verify the scope of the work.
STRUCTRUAL
In new addition area, a vapor retarder shall be placed to retard vapor transmission through the floor slab. (CBC 1907)
Provide page number on each page of the structural calculation.
Sheet S200. Update detail 3B/S123 to the applicable detail. Is it a typo for sheet S132?
Provide and cross-reference drag strut detail from structural calculation into framing plan. The detail shown in structural calculation referenced to 9C/S142 is also not available on the structural drawings.
Please do not submit partial structural calculation as “updated” or “only response to correction comment”. The original structural calculation shall be updated to match the structural design. Provide two copies of complete structural calculation, stamped and signed by the licensed design professional for final approval.
End of comments. No additional corrections marked on the drawings.