HomeMy WebLinkAbout272555_3_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101105911
PROJECT ADDRESS:
1305 W Third St Unit# C
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
U, R-2
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
2/18/2021
INITIAL REVIEW
3/16/2021
EXPIRATION
8/17/2021
RECHECKS:
1.7/12/2021
PROJECT APPLICANT CONTACT PERSON:
2.
Araceli Maciel
3.
TEL:
(714)285-1121
FAX:
VALUATION: $60,000.00
EMAIL:
aramaci65@gmail.com
FLOOD ZONE: X-0602320257J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
-Police Department approval on the corrected/final set of drawings (647-5840).
-Public Works Agency approval (647-5039).
- School District Compliance Certificate; and a copy of the building permit application, signed by
the plan check engineer, shall be required by the School District to verify the scope of the work.
Sheet A-1:
Occupancy Group R-2: Please provide/show the following –
Exterior wall located less than 10-ft from the property line shall be protected with one-hour fire-rated wall assembly. Please show one-hour wall and provide detail reference for one hour fire-rated wall assembly.
2nd Review Comment: Exterior wall locate less than 10-ft from the property line shall be one-hour wall. Please show one-hour wall and provide detail for one-hour wall assembly.
Provide detail for one-hour parapet in compliance with Section 705.11.
2nd Review Comment: The parapet should be extended to the end of the north wall of the rear building. Please revise roof plan A-1 and elevation on A-4.
Parapet must be one-hour and extended minimum 30” above the roof line, including the cricket.
Unprotected opening: Please provide wall opening calculation to show not more than 10% of wall are open.
2nd Review Comment: Unprotect openings shall be limit to 10% of the wall per Table 705.8. Please revise plan to limit wall opening along the east wall line.
Sheet A-2:
On the plan, please show one-hour fire-rated partition between each living unit (unit A & C; Unit C & D). Provide detail reference.
2nd Review Comment: Response was incomplete. Please provide detail to show fire-rated wall extended above ceiling and terminated on the underside of the roof sheathing. Detail shall be clearly cross-referenced onto the plan.
Walls separating dwelling units shall provide airborne sound insulation for walls with an STC rating of at least 50.
2nd Review Comment: Details – Please revise detail to show/provide resilient channels as required for sound insulation.