PLAN CHECK NO:
101107197-198
PROJECT ADDRESS:
2350 S Redhill Ave Bldg# B Parking Structure
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
I B, SPK
OCCUPANCY CLASSIFICATION(S):
A-3, S-2
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
8/3/2021
INITIAL REVIEW
8/27/2021
EXPIRATION
1/30/2022
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Heidi Hare
3.
TEL:
(949)246-0492
FAX:
VALUATION: $20,597,076.00
EMAIL:
heidi@jlhare.com
FLOOD ZONE: X-0602320279J
APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
Non-StructuralReview by
TungLeTle10@santa-ana.org
(714)647-5896
General Instruction and Approval Required
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.
Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.
Resubmit 3corrected sets of plans.
The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process.
- Fire Department approval on the corrected/final sets of drawings ((714)573-6100)
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)
- Grading Permit. Application is made through the Building Safety Division (647-5800) and the plan review is by the Public Works Agency (647-5039)
- School District Compliance Certificate; a copy of the building permit application, signed by the plan check engineer, shall be required by the School District to verify the scope of work. Refer to the attached handout.
Reminder: Parcel map shall be approved and recorded prior to building permit issuance.
Sheet GA0.1.0:
Sheet Index: Plumbing, Mechanical, and Electrical are on a separate review. Please omit the MEP sheets from the Sheet Index.
Please provide a mini set of plan for easy carry around for plan check purposes.
Deferred Submittal: Please include the swimming pool as part of the deferred submittal.
Sheet GA01.1:
Under Code Classification:
The Total Building Area Calculation appears incorrect. Please use the correction Equation 5-3 for each story.
Area of Refuge: Code Exceptions – Please revise code references to show the correct code sections.
Mix Occupancy Allowable Area Calculation: Please correct the code reference to Section 506.2.4.
Parking count: Please confirm Residential Parking spaces are assigned. Otherwise, 5% of the parking spaces shall be accessible.
Sheet GA0.1.2:
UL listed Assembly Table: Please complete Table with referenced details for TPO Roofing. Remove/omit if it does not apply to the project.
Sheet GA1.1:
On the plan, please show (setback) distance between buildings on the same lot, from property lines, and from centerline of streets or public alley.
Please revise construction type to show type I-B (match building data showed on sheet GA01.1).
Egress Plans (Sheet GA1.2 through GA1.5)
On the plans, please clearly show/identify the accessible means of egress elevators that complied with Section 1009.4. (1009.2.1)
Roof Deck Amenity: Please clearly clarify on plan whether the roof deck assembly area would be opened to public or it’s limited to the residential tenants only.
Second tier exit access: Two exits are required for the area on the left ramp parking area. The vehicle ramp leading up to third tier shall not be considered as an exit access. (1006.2.2.5; 406.4.3)
General: Vehicular ramps using as for means of egress: The vehicle ramp may only use for exit for persons using the vehicle parking on that ramp. Please redesign parking so that a person is not required to travel through two (2) consecutive vehicular ramps before reaching the exit stairway.
Exist passageways are part of the means of egress system for the parking structure – The following information are required:
Please provide an exit master plan showing the occupant loads from residential building that’s discharged into the passageway.
Provide passageways enlarged plans showing all requirement dimensions.
Exit passageway shall be unobstructed and maintain the minimum width – please omit/remove the doorway located within the exit passageway. (1024.2)
Residential units within primary entrance that opens into the exit passageway: The exit passageway shall not be used for any other purposes. Please coordinate and revise plan accordingly. (1024.1)
For clarity, please show maximum slope for each vehicle ramp.
Exit passageway: Please coordinate with mechanical plans and provide details for exit passageway ventilation. Exit passageway shall comply with Section 1024.7.
Stairway identification signs complying with Section 1023.9 shall be provided at each floor landing in an interior exit stairway. Details/information shall be clearly cross-referenced onto the plan.
Accessible Path of Travel Plans (Sheet GA1.6 through GA1.9)
Slope ramps serving as part of vertical circulation shall be 5% maximum slope as part of the accessible means of egress. Please coordinate and revise plan accordingly. (1009)
Circulation paths contiguous vehicular traffic shall be physically separated from vehicular traffic per Section 11B-250.1.
On the plan, please provide/show detectable warning between the pedestrian circulation path and vehicular area (parking), including the interior stairway at tier one.Truncated dome provided was incomplete. (11B-247.1)
Floor Plans (Sheet GA2.1 through GA2.7)
Door 107, 114, 125, 115: Rolling doors –
Please specify door shall be tested in accordance with NFPA 252 or UL 10B.
Door shall be equipped with automatic-closing devices.
Sheet GA7.1 & GA7.2: Please specify all fire-rated doors shall have smoke seals.
Elevators: Please show two-way communication in accordance with Section 1009.8.
Door 123 at electrical room: Panic hardware may be required – Please verify panel sizes.
Plan show the diagonal transition lines between the sloped ramps – Please show maximum cross-slope. Where ramps are used for pedestrian circulation shall be 2% cross-slope maximum.
Enlarged Plan (Sheet GA6.11)
Please clearly referenced to the specific details for the accessible restroom information in compliance with Chapter 11B, Division 6.
Provide details for the accessible drinking fountains.
Exterior walls enclosing clubhouse, bathroom facility, equipment rooms, etc. shall be fire-rated in accordance with Table 601. Please revise plan to show fire-rated walls.
Provide fire protection detail for structural frames, including columns for the structure at the amenity deck.
Detailing Sheets
Details shall be clearly cross-referenced onto the plan. Delete/omit detail that does not apply to the project.
Provide details to show transition between the residential building and parking garage with seismic separation required by structural design – at roof, floor, and door, and etc. Details shall be clearly cross- referenced onto the plan.
Provide fire blockings and smoke barriers in the concealed spaces between parking garage wall and residential wall. Details shall be clearly cross-referenced onto the plan.
Sheet GA8.10: On the plan, please provide ICC or UL listing report number for the fire- rated spray material. Provide specification for review and approval.
Provide fire protection detail for structural frames, including columns for the structure at the amenity deck.
Specify on plan, special inspection are required for fire-spray protection.
Provide fire protection details for penetration in fire-rated wall. Detail shall be clearly cross-reference onto the plan.
Sheet GA6.12, Note #A6: Referenced to detail 14, 15/ GA8.4 were not applicable – please provide detail attachment of suspended ceiling.
Provide detail for hard-ceiling finish (ex. Over the restroom area).
Sheet GA9.4 & Sheet GA9.5: Please update notes to reflect and reference to the 2019 Code edition.
STRUCTURAL REVIEW COMMENTS:
Wayne Lee
Wlee@santa-ana.org
(714)647-5848THE FOLLOWING BUILDING PERMIT IS REQUIRED:Submit and obtain building permit (maybe under separate permit) for the design of the ground improvement mitigation method (listed by approved agencies. E.g. ICC) to mitigate the effects of liquefaction and for support of the proposed foundation system. Please note that this soils reinforcement design permit must be approved and issued no later than building permit issuance.PLAN CHECK COMMENTSPlease refer to plan check set for plan check comments not shown in this list.Please provide address on the title block on each sheet. (Refer to architectural sheets for address)Provide sheet index on sheet GS1.1.On sheet GS1.1, list all structural deferred submittal items on cover sheet. (e.g. stairway construction).Sheet GS2.8A. Please justify the column cap design and dimensions at the middle columns where two columns shared with one cap. (e.g. Grid F,5 and F,7.)Sheet GS2.8A. A column cap is shown between the concrete shear wall and PT slab in the pool. Please clarify the column location and if this detail is applicable. (e.g. Grid E,5.)Sheet GS2.8A. Please add a note on plan to specify the column cap dimensions located at the edge of the slab. E.g. Grid A, 5.7.Provide and cross-reference complete PT-slab design at the amenity level (e.g. calculation page 198 through 207 at grid 4.5, 8, 8.8, 10) on plan. Provide strand design information including minimum Fe force.Clarify the strand position at each column from the bottom of the bend beam on each level (e.g. refer to grid line 3 sheet GS2.7 and calculation page 102. Is it 9.75” from the bottom of the bend beam? Plan shows 6.25”). Please check each grid where bend beam occurs.Clarify if the end span in the calculation (e.g. page 142) on grid line 10 on each level. Is 8 feet end span correct?Provide slab bend beam design on grid line B at each level. (e.g. sheet GS2.6A). Cross-reference beam construction details and verify the reinforcement, strand location…on plan.Revise plan to call out Pe force and number of strands of the PT-slab along grid line B.3. (e.g. sheet GS2.6 / calculation page 154)Sheet GS7.1, Beam B-1 design. Per calculation page 262, minimum As-6.93 in^2. The provided 4-#11 has 6.24 in^2. Please check the reinforcement amount and clarify on the beam elevation.Cross-reference missing detail at the stairway #2 on grid #9 and #B.4. (e.g. GS2.5A and other sheets)LateralPlease justify the lateral design for Type 3 of the horizontal structural irregularities per ASCE 7-16 Table 12.3-1 at the split level ramp diaphragm. Please justify the lateral design for Type 2 of the vertical structural irregularities per ASCE 7-16 Table 12.3-2 occurs at the amenity level and adjacent level.Show redundancy factor value, ρ, on the structural cover sheet under general notes. For concrete shear wall design, please show justification in the structural calculation if the value is taken as 1 instead of 1.3. (ASCE 12.3.4.2)The occupant load is greater than 300 at the rooftop amenity area. Please verify and clarify with the architect that whether or not the primary occupancy is public assembly in the garage building and building may be classified as Risk Category III. The current structural design is Risk Category II. (CBC Table 1604.5)Please provide additional analysis to justify split ramp diaphragm. Currently the diaphragm is analysis as a single diaphragm.Seismic Drift (ASCE Section 12.12.1): Calculate seismic drift based on deflections of each level with Cd and I factors using strength level forces per ASCE 7 Section 12.8.Separation (ASCE 7 Section 12.12.3): Provide separation justification from adjacent structure(s) on the same property meeting ASCE 7 Section 12.12.3. In the calculation, please also include a copy of floor plan indicating building separation distance between garage and apartment building on all sides.Specify minimum shearwall length on each shear wall on plan.Clarify the tie spacing at grid A shear wall grade beam (e.g. sheet GS5.3 / calculation page 489). #7@12” o.c.?FoundationClarify the extent of the ground improvement area. Please attach the ground improvement drawings to the structural plans for reference.Provide the design of the ground improvement mitigation method (listed by approved agencies. E.g. ICC) to mitigate the effects of liquefaction and for support of the proposed conventional foundation system.Provide the design of the ground improvement mitigation method (listed by approved agencies. E.g. ICC) to mitigate the effects of liquefaction and for support of the proposed conventional foundation system.Show on the tile sheet the name, address and phone number of the Project Geotechnical Consultant and a list of all applicable geotechnical reports, including the addendum of the soils report, dated on March 11, 2021.Please review and revise the title sheet and foundation design based on the recommended allowable soil bearing capacity. The addendum to of the soils report limited the allowable soils bearing pressure to 5,000 psf for the design of the conventional foundations, supported on the stone columns. (current design is based on 7,000 psf)Call out reinforcement size and spacing in the 5” slab-on-grade concrete slab.Per amendment of soils report, all isolated column pad footing shall be connected in at least two directions by grade beams. Please update foundation design. (e.g. interior column location)Add note to the cover page of the structural plans that “The design of the ground improvement mitigation method to mitigate the effects of liquefaction and for support of the proposed foundation system shall be designed by a licensed professional and reviewed and approved by the geotechnical engineer and the structural engineer in record”.Foundation design shall be reviewed by the geotechnical engineer. Geotechnical report recommendations are considered to be minimum standards. Structural calculations and drawings must meet or exceed said minimum standards. Verification of review may be by a “review stamp” on the foundation plan or by a letter on their letterhead. (1803)Retaining wallPlease provide a wall legend and key plan in the calculations, identify the walls calculated, and cross-reference to the details/schedules on the plans. (e.g. elevator pits, garage walls at ramp…)Clubhouse / fitnessPlease provide CMU shear wall design, reinforcement, length and details on the framing plan and make cross-reference with the structural connection details. END OF COMMENTS