Loading...
HomeMy WebLinkAbout275752_3_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101106879 PROJECT ADDRESS: 630 S Grand Ave Unit# 114 PLAN CHECK ENGINEER: Lee, WayneTEL:714 647-5848 EMAIL: wlee@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B, SPK OCCUPANCY CLASSIFICATION(S): B, F-1, S-1 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 6/7/2021 INITIAL REVIEW 6/11/2021 EXPIRATION 12/4/2021 RECHECKS: 1.08/13/2021 PROJECT APPLICANT CONTACT PERSON: 2. Miguel Lamas 3. TEL: (951)906-3143 FAX: VALUATION: $17,000.00 EMAIL: miguel@lamascom.com FLOOD ZONE: X-0602320276J APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS(Information only) The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Fire Department approval on the corrected/final sets of drawings ((714)573-6100) - County of Orange Health Department approval on the corrected/final set of drawings ((714)433-6000)Balance of correction comments:Sheet A0-0. Show designer’s physical address in the directory. Sheet A0-0. Under the scope of work, add to the description Item #2 Alter 248 sf T-bar ceiling in office and mixing room.Item #3 Add 660 sf. T-bar ceiling.Sheet A0-1. Add wording on signage #12 on plan.Tactile exit signs shall be required at the following locations: (see redmarks) - Each grade-level exterior exit door shall be identified by a tactile exit with the word “EXIT.” - Each exit access door from an interior room or area to a corridor or hallway, which is required to have a visual exit sign, shall be identified by a tactile exit sign with the words “EXIT ROUTE.”Sheet A0-1. Reduce the partition wall length to create 60 inches horizontal clearance on the door pull-side. See red lines on the drawing.Sheet A0-4. Revise drawing to show operable parts of such hardware shall be 34 inches minimum and 44 inches maximum above the finish floor or ground. Sheet A0-4. Revise unisex wall-mounted signage and door mounted signage details. Refer to attached DSA bulletin BU 17-01 for signage drawing. Please update the plan.Sheet A0-4. Revise mounting height for wall-mounted signage. Tactile characters on signs shall be located 48 inches minimum above the finish floor or ground surface, measured from the baseline of the lowest Braille cells and 60 inches maximum above the finish floor or ground surface, measured from the baseline of the highest line of raised characters. Refer to Figure 11B-703.4.1. (11B-703.4.1).Refer to red lines on the drawings for additional plan check comments which are not shown on this list. END OF COMMENTS