HomeMy WebLinkAbout274849_2_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101106607
PROJECT ADDRESS:
100 S Elk Ln
PLAN CHECK ENGINEER:
Lee, WayneTEL:714
647-5848
EMAIL:
wlee@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
I A, III B, SPK
OCCUPANCY CLASSIFICATION(S):
A-2, A-3, B, R-2, S-2
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
5/7/2021
INITIAL REVIEW
5/25/2021
EXPIRATION
11/3/2021
RECHECKS:
1.09/29/2021
PROJECT APPLICANT CONTACT PERSON:
2.
Lisa Zoscak
3.
TEL:
(949)338-4189
FAX:
VALUATION: $180,000.00
EMAIL:
lisa@aquatictechnologies.com
FLOOD ZONE: X-0602320276J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.
Please see corrections on submitted plans. Red marked set must be returned with revised plans. Plans resubmitted without the red markup set may result in delayed review time and additional plancheck fees.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
-Public Works Agency approval (647-5039).
-Health Department approval.
PLAN CHECK COMMENTS
STRUCTURAL
All structural drawings and structural calculation shall be prepared, stamped, and signed by a California licensed architect or registered professional engineer.
Provide structural calculation and detail for the wall framing and anchorage to the podium slab of the pool enclosure walls, which are shown on the landscape plan: (CBC, ASCE 7-16)
Detail C/LC.7.
PC2: The structural design refers to structural detail 13/1SL-2.0. Provide structural calculation to verify structural design and anchorage.
Detail A/LC.19.
Detail A/LC.11.
Detail A/LC.13.
PC2: The structural design refers to structural detail 13/1SL-2.0. Provide structural calculation to verify structural design and anchorage.
Detail A/LC.16.
PC2: Detail 5/1SL-2.0. Clarify the CMU wall. Plan shows 8”, but calculation requires 12” nominal thickness. Please clarify on plan and calculation to be consistence.
END OF COMMENTS