HomeMy WebLinkAbout279554_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101108022
PROJECT ADDRESS:
20 Civic Center Plz
PLAN CHECK ENGINEER:
Lee, WayneTEL:714
647-5848
EMAIL:
wlee@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
I A
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
9/21/2021
INITIAL REVIEW
9/23/2021
EXPIRATION
3/20/2022
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Gaby Lomeli
3.
TEL:
(714)559-1788
FAX:
VALUATION: $900,000.00
EMAIL:
glomeli@santa-ana.org
FLOOD ZONE: X-0602320276J
APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Please return marked up set of drawings with corrections.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Fire Department approval on the corrected/final sets of drawings ((714) 573-6100)- Public Works Agency approval (647-5039)Specify a heavy duty suspended ceiling T-bar grid system with ICC number. [ASCE 7, Sec. 13.5.6.2.2]Show minimum 2 inch wide angle closer. One end of the ceiling grid shall be attached to the closure angle. The other end in each horizontal direction shall have a 0.75 inch clearance from the wall and shall be free to slide on a closer angle. (ASCE 7-16 Section 13.5.6.2.2.)Per detail 7/A501, provide bracing anchor details on plan and make cross-reference into detail 7/A501 where bracing detail can be found. Details are required for attachment parallel and perpendicular to flutes.EGRESSCBC Section 1004.3, Posting of occupant load. Every room or space that is assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent. Provide signage within the following room: (1) conference room #1 (247), (2) conference room #2 (262), and (3) breakroom (245).Add note to plan:” CBC Section 1020.5, Air movement in corridors. Corridors shall not serve as supply, return, exhaust, relief or ventilation air ducts when required to be fire-resistive rated in accordance with Table 1020.1.”Sheet A-122. Provide exit signs at each turn of the egress path. The exit signs shall be readily visible from any direction of egress travel and clearly indicate the direction of egress travel. See red marks on sheet G-008. [CBC 1013] See redmarks for the requested locations.ACCESSIBILITYAdd note to door schedule: “Handles, pulls, latches, locks, and other operable parts on doors and gates shall comply with 11B-309.4 Operation. Operable parts of such hardware shall be 34 inches minimum and 44 inches maximum above the finish floor or ground. Where sliding doors are in the fully open position, operating hardware shall be exposed and usable from both sides. §11B-404.2.7.”END OF COMMENTS