HomeMy WebLinkAbout272421_3_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101105880 PROJECT ADDRESS: 925 1/2 Dianne St PLAN CHECK ENGINEER: Le, TungTEL:714 647-5896 EMAIL: Tle10@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): R-3, U PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 2/12/2021 INITIAL REVIEW 3/10/2021 EXPIRATION 8/11/2021 RECHECKS: 1.6/14/2021 PROJECT APPLICANT CONTACT PERSON: 2.11/9/2021 Mayra Cabrera 3. TEL: (951)315-3903 FAX: VALUATION: $8,000.00 EMAIL: mayra.a.cabrera@att.net FLOOD ZONE: X-0602320164J Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.Instruction and Approval RequiredAll items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans. Plans shall be signed and dated by the responsible designer. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: -Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. -Police Department approval on the corrected/final set of drawings (647-5840). -Public Works Agency approval (647-5039). - School District Compliance Certificate; and a copy of the building permit application, signed by the plan check engineer, shall be required by the School District to verify the scope of the work. The responses were incomplete. The following comments are remain applicable: Final plans shall be signed and dated by the person who is responsible for the construction document. Sheet A.1: New landscape planter adjacent to the existing garage door – Please show section to show exposed earth/grade located at least 8” below the wall sill plate and show surface water flow away from the building wall. Sheet A.3: existing 36”x36” at bedroom shall be replaced with a 48”x48” slider for emergency escape window openings. Provide construction detail for the interior wall. Show attachment at top and bottom of wall. Details shall be clearly cross-referenced onto the plan. Detail 2/S.1, one-hour wall: Please revise detail to show 5/8” type ‘X’ gypsum board on both sides of wall, and fire-rated wall shall extended from slab/floor to the underside of roof sheathing. Detail 1/S.2: Please clearly show attachment of new wall studs to the exiting header. Show mean of attachment, including fastener. Detail 1/S.2: Please clearly show attachment detail of new wall to foundation, including anchor bolts, spacing, minimum embedment, etc. New footing is required at the existing garage door opening; now with an infilled wall. Coordinate and revise detail accordingly. On the plan, please specify R-13 insulation at wall and R-30 insulation at roof. Please show ceiling frames for ceiling finish (drywall) and support. Show ceiling joist size, spacing, bearing (supporting) location, etc. Plan show existing moisture barrier underneath the existing garage slab was not accurate. Typically, moisture barrier was not provided under the existing garage slab. Approved surface application may be used. On the plan, please provide manufacturer’s name and ICC report number on the plan.