HomeMy WebLinkAbout271909_3_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101105754-55 PROJECT ADDRESS: 4713 1/2 W Floyd Cir PLAN CHECK ENGINEER: Le, TungTEL:714 647-5896 EMAIL: Tle10@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): R-3, U PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 1/27/2021 INITIAL REVIEW 2/26/2021 EXPIRATION 7/26/2021 RECHECKS: 1.8/25/2021 PROJECT APPLICANT CONTACT PERSON: 2.12/2/2021 Giep Van Le 3. TEL: (323)537-5874 FAX: VALUATION: $100,000.00 EMAIL: gieple49@gmail.com FLOOD ZONE: A-0602320256J Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: -Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. -Police Department approval on the corrected/final set of drawings (647-5840). -Public Works Agency approval (647-5039). - School District Compliance Certificate; and a copy of the building permit application, signed by the plan check engineer, shall be required by the School District to verify the scope of the work. -Grading Permit. Application is made through the Building Safety Division (647-5800) and the plan review is by the Public Works Agency (647-5039). This project is in a special flood hazard area designated on the flood insurance rate map (FIRM) as zone A. Hydrology study and Elevation Certificate are required. 2nd Review Comment: Elevation Certificate and BFE determination document were provided – The following comments are required: Two (2) separate elevation certificates (EC) are required; one for main house (4713 W. Floyd Cir.), and one for the proposed detached ADU (4713 – 1/2 W. Floyd Cir.). Please making sure the job address on Section A2 is match with the building address. Section A8 & A9: Please complete (fill in) all empty space. Use “N/A” if it’s not applicable. Final EC shall be reproduced / imprinted onto the plan. Printout must be legible on plan. 3rd Review Comment: Required information above were not provided. Please provide updated EC with the required information above. Structural Review Comment: 3rd Review Comment: Structural response was incomplete. The following comments remain applicable and has been rewritten. Sheet S-1 (Main house): The 4x6 header over the opening between new family and dining room was overstressed – Please upsize. Sheet S-3 (ADU): the 4x16 ceiling beam over the living room – Structural calculation was not provided for this beam. Please design beam for roof + ceiling loads; also, include the roof-mounted PV system loads. Sheet S-3 (ADU): Please reference detail 8/SD-1 to the interior bearing wall. Sheet S-3 (ADU): Detail 10/SD-2 – Please revise detail to show braces or cripple wall supporting roof rafters above. Reminder: Please transfer geotechnical engineer “review” stamp to the final plan prior to submitting to Building & Safety for final review and approval. Structural calculation: Please provide two complete sets of updated calculation package for final review and approval. Partial package is not allowed.