HomeMy WebLinkAbout281594_1_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101108633
PROJECT ADDRESS:
302 S Broadway Unit# B2
PLAN CHECK ENGINEER:
Huang, GaryTEL:714
647-5862
EMAIL:
Ghuang@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
U, R-2
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
11/18/2021
INITIAL REVIEW
12/20/2021
EXPIRATION
5/17/2022
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Nash Levy
3.
TEL:
(323)352-7727
FAX:
VALUATION: $25,000.00
EMAIL:
nash.levy@feldandassociates.com
FLOOD ZONE: X-0602320276J
GUIDELINES:
Comments contained within this report reflect only those of the Building and Safety Division. Additional comments or corrective action may be required by other Departments and/or outside Agencies
This Plan Review Report and all subsequent code references are based upon the most recent version(s) of the 2019 California Building Codes (CBC, CRC, CFC, CEC, CPC, CMC, CGBSC, and CEES)
The approval of plans and any supporting documents does not permit the violation of any section of the adopted building codes or other pertinent local ordinances, or state and federal laws
All listed plan review comments must be adequately addressed before a building permit can be issued
Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.
PLAN REVIEW COMMENTS:
Applicant shall address all the checked‘☒’ correction comments below before resubmitting plans to Building Safety for recheck.
☒1. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
☒Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process.
☐Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700).
☒Police Department approval on the corrected/final set of drawings (647-5840).
☒Public Works Agency approval (647-5039).
☐Proof of Worker's Compensation Insurance shall be required at the time of permit issuance.
☒School District Approval; and a copy of the school fee worksheet, completed by the plan check engineer, shall be required by the School District to verify the scope of the work.
☐Grading Permit. Application is made through the Building Safety Division (647-5800) and the plan review is by the Public Works Agency (647-5039).
☒2. Note on plan: All concealed work installed without permits must be exposed for inspection to the satisfaction of the Building Inspector. This includes methods of attachment and all footings, structural members, mechanical, electrical, plumbing and insulation.
☒3. Provide the following design data on the first sheet
☒Construction shall comply with the 2019 CRC, CBC, CPC, CMC, CEC, California Green Building Code, and California Energy Efficiency Standards Code editions.
☒All drawings and supporting document shall be prepared, stamped and signed by a California licensed architect or registered professional engineer. (CRC R301.1.3, CBC 107.1 and 107.3.4)
☒4. Note on plan: Mechanical, electrical and plumbing are not part of this plan review and approval. MEP are subject to building field inspection.
☒5. Room dimensions –
☒Specify on the plans 7 feet 6 inches ceiling height above the finished floor for habitable space, hallways. Laundry room, bathroom, toilet room, and un-habitable basements shall have ceiling height not less than 7ft. (CBC1003.2, CBC1207.2)
☒6. Every dwelling unit shall be provided with heating facilities capable of maintaining a room temperature of not less than 68°F (20°C) at a point 3 feet (914 mm) above the floor and 2 feet from exterior walls in habitable rooms at the design temperature. The installation of one or more portable space heaters shall not be used to achieve compliance with this section. (CBC1203.1)
☒7. Emergency escape and rescue openings
☒The escape opening shall have a minimum net clear opening of 5.7 sq. ft. with 24" minimum net clear height and 20" minimum net clear width. Escape window shall have a finished sill height not more than 44" above the floor. At grade-floor is allowed to have escape opening of 5.0 sq. ft. (CBC1030.2, CBC1030.3)
☒8. Means of egress / Doors – (CBC1010.1.6)
☒On the plan, provide a landing or floor on each side of each exterior door. Landing shall have width of not less than the door served and a minimum of 44” measured in the direction of travel.
☒Thresholds at doorway shall not exceed ¾” in height above the finished floor
Energy Conservation – Title 24 Energy forms & calculations
☐1. Provide documentation to demonstrate compliance with the California Energy Code.
☐2. Climate zone 8 is used.
☐3. Compliance forms with signatures must be provided on plans.
☒4. Kitchen shall be vented to the outside. On the plan, please show exhaust fan(s) in kitchen (100 cfm minimum).
☐5. Provide building sections to show building envelope, including wall, floor, and roof/ceiling insulation, per Title 24 calculation.
CalGreen Plan Review Comments:
☒1. Provide CalGreen information based on 2019 California Green Building Standard Code, City of Santa Ana does not recognize LADBS requirements
Structural Plan Review Comments:
☒1. Existing garage converted into ADU (habitable space):
☒Provide ceiling framing plan to show supporting of new ceiling drywall. Additional ceiling joists may be required. Provide details and clearly cross-reference detail onto the plan. ☒Provide/show lateral support for the proposed ADU.
☒Provide construction details for the infilled wall at the existing garage door opening. Show attachment at top and bottom of wall. Provide concrete curb (stem wall) at existing door opening.
☒Provide moisture barrier for the existing concrete slab.
☒ Provide structural material notes on plan (i.e. lumber species & grade, steel reinforcement grade, and concrete compressive strength, etc)
☒ Provide new footing over existing garage door opening
☒ Provide window header size & typical opening framing detail(s)
☒ Provide structural foundation, floor framing plans, and connection details
☒ Provide structural calculation for gravity and lateral design☒Additional Review Comment:
Sheet A1.1, proposed floor plan: provide 1 hour window at the ex. Corridor per CBC table 716.1(2)
Sheet A1.1, proposed floor plan: Indicate location of the heating unit on plan
Sheet A1.1, proposed floor plan: identify whether existing building equipped with fire sprinkler
Sheet A1.1, proposed floor plan: provide correct references
Sheet A1.1, proposed floor plan: provide building section and indicate floor framing, wall assemblies, etc.
Sheet A1.1, plan legend: detail 4/D000 shows 2x4 stud at 16” o.c. coordinate detail(s)
Sheet D000, detail 1: provide curb reinforcing and rebar edge distance
Sheet D000, detail 1: provide header size
Sheet D000, detail 1: notes indicate existing roofing, should it be floor assemblies? Revise detail
Sheet D000, detail 4: verify shot pin call out with ICC report. Provide correct shank diameter and embedment
Sheet D000, detail 4: provide missing joist framing
Red marked comment set is available to pick-up at the City Hall. (End of Comment)