HomeMy WebLinkAbout281531_1_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101108605 PROJECT ADDRESS: 2400 S Pullman St Unit# A PLAN CHECK ENGINEER: So, AnsonTEL:714 647-5830 EMAIL: aso@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: III B, SPK OCCUPANCY CLASSIFICATION(S): F-1 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 11/19/2021 INITIAL REVIEW 2/1/2022 EXPIRATION 5/18/2022 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Ron Vandermooren 3. TEL: (714)357-1230 FAX: VALUATION: $10.00 EMAIL: ron@rvmconstruction.com FLOOD ZONE: X-0602320278J APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5830 for an appointment.Sheet A-1Update building code edition to “2019” under Building Department Notes section - note number 3 and the note below note number 16.Under Project Information, specify the occupancy group and floor area for suite A and suite B separately. A sticky note is attached on the title sheet. It states:” Additional Bathrooms with standard ADA requirements will be required along with separate electrical metering for the new suite B”. The city is requiring plumbing fixture calculations, bathroom accessibility design, and electrical metering design to be provided on this permit.Sheet A-2Enlarge texts on the site plan. The notes are illegible.Erase “AREA OF WORK” on the site plan and on the aerial map.Suite A and B must have its own independent ingress and egress path. Show the accessible Path of Travel from the accessible parking space to the entrance of suite A and B.Sheet A-3Label each room throughout the plan.The floor plan shows stairways. Provide the second-floor plan for reference. In addition, Project Information on sheet A-1 indicates a one-story building. Is this a one or two story building?Show the door location south of the male and female restrooms.Provide note on the existing demising wall:” Existing one-hour fire rated wall to be verified in field.”Show electrical metering room in suite A and suite B. It appears the existing electrical room in suite B is missing on plan. Each suite shall have its own access to electrical, disconnect, circuit breakers…etc.Provide accessible bathroom design and details per comment number 7.