Loading...
HomeMy WebLinkAbout276832_4_Corrections.docxSPC PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101107166-71 PROJECT ADDRESS: 1821 N Grand Ave PLAN CHECK ENGINEER: Lee, WayneTEL:714 647-5848 EMAIL: wlee@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B, SPK OCCUPANCY CLASSIFICATION(S): A-3, B, E PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 7/19/2021 INITIAL REVIEW 7/29/2021 EXPIRATION 1/15/2022 RECHECKS: 1.10/05/2021 PROJECT APPLICANT CONTACT PERSON: 2.11/21/2021 Tony Pacheco-Taylor 3. TEL: (949)774-2906 FAX: VALUATION:$3,170,000.00 EMAIL: tonyp@bcaarchitects.com FLOOD ZONE:X-0602320163J APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTSThe applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. - Fire Department approval on the corrected/final sets of drawings ((714) 573-6100). - Police Department approval on the corrected/final set of drawings (647-5840). - Public Works Agency approval (647-5039). - Grading permit - School District Compliance Certificate. A copy of the building permit application, signed by the plan check engineer, shall be required by the School District to verify the scope of work. Refer to the attached handout.Scope of work. In addition to total 16022 sf for the school building, show overall building area on each level. Indicate if the exterior stairway are part of the 16022 sf. area.PC2: Cover sheet. Please update description of the scope. Please do not refer the required information. PC3: Provide area breakdown on the cover sheet. (gross area including walls) Show area break down on each level. This is for building permit.For school fee calculation purpose, show square footage of covered and enclosed space only as assessable square footage. (Refer to school district fee handout)Please clarify the allowable area calculation on sheet A0.5. Clarify on plan the actual area of each group and ensure the ratio of each level does not exceed 1.EGRESSProvide illuminated and tactile signs in the shade structure on the plan.PC2: This is an E occupancy space with minimum 2 exits required. Please revise plan to provide signage.PC3: Plans are not revised. Since 2 exits are required, then signage is required. (CBC 1013).ACCESSIBILITYENERGY This building is subject to the 2019 State of California Energy Conservation Regulations. Submit T-24 drawings to show compliance: Submit two signed copies of T-24 energy calculations in compliance with 2019 Energy Standards.Submit T-24 drawings in compliance with 2019 Energy Standards.Architectural and structural drawings have to be consistent with building envelope energy design.PC2:Sheet A0.10. The last page of NRCC-CXR-E form shall be completed and signed.PC3: Not done.Provide CRRC number on plan for the proposed roof covering to meet the following requirement: minimum reflectance: 0.63 and minimum emittance: 0.75.PC3: Provide CRRC number on plan. END