HomeMy WebLinkAbout282679_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101108993
PROJECT ADDRESS:
1951 E Dyer Rd Unit# F
PLAN CHECK ENGINEER:
Lee, WayneTEL:714
647-5848
EMAIL:
wlee@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
III A, SPK
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
12/22/2021
INITIAL REVIEW
1/17/2022
EXPIRATION
6/20/2022
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Lydia Khouri
3.
TEL:
(213)357-2151
FAX:
VALUATION: $5,000.00
EMAIL:
office@coliveriadesign.com
FLOOD ZONE: X-0602320278J
APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Public Works Agency approval (647-5039)Sheet A0.0. Revise type of construction to IIIA.Sheet A2.1. Tactile exit signs shall be required at the following locations:
- Each grade-level exterior exit door shall be identified by a tactile exit with the word “EXIT.”Sheet A2.1. Note the following on the plans: “The means of egress, including the exit discharge, will be illuminated to a level of not less than one foot-candle at the walking surface at all times the building space served by the means of egress is occupied”.Sheet A2.1. Note on the plans: “Exit signs shall be internally or externally illuminated at all times. Externally illuminated exit signs shall be connected to an emergency power system (batteries, unit equipment or an on-site generator) that will automatically illuminate the exit signs for a duration of not less than 90 minutes in case of primary power loss.”Sheet A2.1. Note on plans: “Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.”Sheet A2.1. Exit doors equipped with a key operated locking device shall have a readily visible, durable sign posted on the egress side adjacent to the door stating: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. The sign shall have one-inch high letters on a contrasting background.Sheet A2.1. Locate the exit signs at the hallway and exit door(s) such that no point in the corridor/exit passageway is more than 100 feet or the listed viewing distance for the sign, whichever is less.Sheet A2.0. Revise door width on door #3. Door openings shall provide a clear width of 32 inches minimum. The 2’-8” wide door does not work. (11B-404.2.3)Sheet A2.0. Door #3 in the massage room shall have 60” minimum landing length in the direction of the door swing. (11B-404.2). Provide dimension on plan to justify.Sheet A2.0. Show minimum 18” measured from the sidewall to the centerline of the lavatories. Show dimensions on the breakroom and the facial room lavatories.Symbols shall comply with the following:Doorways leading to toilet rooms and bathing rooms shall be identified by a geometric symbol complying with 11B-703.7.2.6 Toilet and Bathing Facilities Geometric Symbols. The symbol shall be mounted at 58 inches minimum and 60 inches maximum above the finish floor or ground surface measured from the centerline of the symbol. Where a door is provided the symbol shall be mounted within 1 inch of the vertical centerline of the door. (11B-703.7.2.6)Provide accessible restroom signage. Unisex toilet and bathing facilities shall be identified by a circle, ¼ inch thick and 12 inches in diameter with a ¼ inch thick triangle with a vertex pointing upward superimposed on the circle and within the 12-inch diameter. The triangle symbol shall contrast with the circle symbol, either light on a dark background or dark on a light background. The circle symbol shall contrast with the door, either light on a dark background or dark on a light background. (11B-703.7.2.6.3)Add note to grab bar. The space between the grab bar and walls/projecting objects shall be 1-1/2 inches minimum. (CBC 11B-604.5, 11B-609.3)END OF COMMENTS