HomeMy WebLinkAbout278993_4_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101107835
PROJECT ADDRESS:
1013 N Elaine Dr Unit# 2
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3, U
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
9/9/2021
INITIAL REVIEW
9/22/2021
EXPIRATION
3/8/2022
RECHECKS:
1.11/29/2021
PROJECT APPLICANT CONTACT PERSON:
2.12/21/2021
Trang Ho
3.
TEL:
(714)213-1608
FAX:
VALUATION: $90,000.00
EMAIL:
onetrang10@gmail.com
FLOOD ZONE: A-0602320143J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
-Police Department approval on the corrected/final set of drawings (647-5840).
-Public Works Agency approval (647-5039).
- School District Compliance Certificate; and a copy of the building permit application, signed by
the plan check engineer, shall be required by the School District to verify the scope of the work.
-Grading Permit. Application is made through the Building Safety Division (647-5800) and the
plan review is by the Public Works Agency (647-5039).
Flood Zone A:
This project is in a special flood hazard area designated on the flood insurance rate map (FIRM) as zone A. Please provide the following:
Elevation Certificate: Please revise job address to reflect plan (1013 N. Elaine Dr., Unit #2.
2nd Review Comment: Please revise job address on the EC as requested.
3rd Review Comment: Revised EC was no provided. Please comply with the comment above.
Final Elevation certificate (EC) shall be reproduced/imprinted onto the plan.
2nd Review Comment: Please comply as required above.
3rd Review Comment: Revised EC was not provided on the plan. Please comply with the comment above.