Loading...
HomeMy WebLinkAbout282422_1_Corrections.docxPLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101108904 PROJECT ADDRESS: 653 N Poinsettia St PLAN CHECK ENGINEER: Le, TungTEL:714 647-5896 EMAIL: Tle10@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): B, M, R-2 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 1/28/2022 INITIAL REVIEW 3/15/2022 EXPIRATION 7/27/2022 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Samuel Ghaly 3. TEL: (949)235-0552 FAX: VALUATION: $1,500.00 EMAIL: sam_ghaly@yahoo.com FLOOD ZONE: X-0602320163J Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: -Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. - Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700). -Police Department approval on the corrected/final set of drawings (647-5840). Sheet A-2 & A-3: Please show door openable (panic hardware) parts locate at 34” minimum and 44” maximum above the finish floor or ground. On the plan, please specify the force for pushing or pulling open a door/gate shall not exceed 5 pounds. Show minimum 10” smooth surface on the push side of the swing gate/door surface, measured from the finish ground. Please provide plan to show level landing and maneuver space on both sides of the gate/door. Provide minimum 60” clear landing with 24” clear from the gate/door strike edge, on the pull side; and 48” minimum clear landing with 12” clear from the gate/door strike edge, on the push side. Reminder: Final plan shall be stamped, singed, and dated by the engineer of record. Orange County Fire Authority approval is required. Please submit plan to OCFA for review and approval.