HomeMy WebLinkAbout280207_3_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 103108215 PROJECT ADDRESS: 501 W Dyer Rd PLAN CHECK ENGINEER: Lee, WayneTEL:714 647-5848 EMAIL: wlee@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): B, F-1, S-1 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 10/8/2021 INITIAL REVIEW 10/24/2021 EXPIRATION 4/6/2022 RECHECKS: 1.01/07/2022 PROJECT APPLICANT CONTACT PERSON: 2. Michael S Jones 3. TEL: (310)466-8321 FAX: VALUATION: $575,000.00 EMAIL: mjones@sidleyjonesinc.com FLOOD ZONE: X-0602320278J APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Please return marked up set of drawings with corrections.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Fire Department approval on the corrected/final sets of drawings ((714)573-6100) - Public Works Agency approval (647-5039)PLAN CHECK COMMENTSSheet A0.00. Transpose all hand-writing scope of work items into the drawings. Sheet A0.00. Update type of construction per CBC chapter 6. Type VN is not recognized in 2019 CBC. Sheet A0.00. Clarify the occupancy of all storage area to either S1 or S2. Provide a list of storing material in the storage area on plan to verify and comply with occupancy group in CBC section 311. (CBC chapter 3)Sheet A0.00. Clarify the occupancy of F2 per CBC 306. Provide evidence to prove the occupancy use is F2 in shop area. Submit a letter addressed to the Building Safety Division describing in detail the manufacturing process from material delivery, storage, handling, packaging, and shipping of finish product. Include an equipment list describing use in the process. Occupancies storing, handling, using, and/or selling hazardous materials, liquids, and chemicals shall submit a list of all said materials, listing their quantities and how they relate to specific California Building Code Table items. Note on the Floor Plan, type and quantity of hazardous material in each control area and fire-resistive rating for fire barriers. (307, 414)Sheet A0.00. Specify on plan if the building is equipped with Automatic Fire-Sprinkler system on the cover sheet.(note that this plan check assuming this is a non-sprinklered building)Sheet A0.00. Summary/ analysis. Show total building square footage for existing floor area and proposed floor area separately. Clarify whether the existing 8112 sf. (item #2) including mezzanine addition or not.Sheet A0.00. Show existing, new addition and total __ sf. mezzanine in the scope of work.Sheet A0.00. Add 2019 California Green Building Standards Code (CALGreen) to the governing Codes. Sheet A0.00. Provide a Building Code Analysis on the title sheet. Include the following code information for each building proposed: Description of use, Occupancy, whether separated or un-separated, number of stories, type of construction, sprinklers, floor area, height, and allowable floor area.Show hourly fire rating of fire barrier or fire partitions in the wall legend. While cross-reference to sheet A6.00, provide tested and approved fire assembly details.Sheet A3.10. Provide complete floor plan of the first floor.Clarify the use of the shop (124) and warehouse (125). Provide more information on plan, including equipment, furniture, racks...identify any type and amount of hazardous material stored on site. Justify this is not an H occupancy building. (CBC 307, 414 and 415) MEZZANINIEIf horizontal assembly is required between mezzanine and first floor, provide assembly details with __ hour fire rating on plan. (e.g. occupancy separation per CBC Table 508.4, rated corridor ceiling…)Sheet A4.00. Clarify and show height of ceiling in each building sections. Sheet A3.20. Show ceiling height on the mezzanine reflected ceiling plan on each space/room. The clear height is 7’-6” minimum except the area above and below the mezzanine floor construction shall be not less than 7 feet (505.2). Note that Section 1 shows 6’-10” ceiling height does not meet mezzanine definition. Revise design to comply with building code. (1003.2)PC2: Part of the mezzanine (storage #201 and storage room #202) still does not have 7 feet minimum ceiling height. Refer to section 5/A4.00 and mezzanine plan on sheet A3.10. Please update the design to comply with Code. Please contact Plan reviewer to discuss.FIRE PROTECTIONProvide on the drawings a complete “fire resistance design schedule” which shall include the following: - The building elements which require fire-resistive construction. - The hourly rating of the building element as required by the Code. - Evidence of appropriate fire resistance for each building element in accordance with specific UL listing or ICC Evaluation Report for each material selected. Evidence shall include appropriate material thickness for each building element. - Non-standard fire-resistive designs requiring adhesives, overcoats, metal lath-netting, or special thicknesses shall be detailed.Plans shall indicate how required structural and fire resistive integrity will be maintained where a penetration will be made for electrical, mechanical, plumbing and communication conduits, pipes and similar systems. CBC Section 106.1.1 and CBC Chapter 7. Note on the plans the ICC Research Report number, U.L. number, State Fire Marshal number, or approval number of another agency accepted by the City of Santa Ana.CBC Section 718.2.2, Provide fire blocking in concealed spaces of stud walls and partitions, including furred spaces at the ceiling and floor level and at 10 ft. intervals both vertical and horizontal.Fire blocking. In combustible construction, fire blocking shall be installed to cut off concealed draft openings (both vertical and horizontal) and shall form an effective barrier between floors, between a top story and a roof or attic space. Fire blocking shall be installed in the locations specified in CBC Sections 718.2.2 through 718.2.7.CBC Section 708.4, Fire partitions shall extend from the top of the foundation or floor/ceiling assembly below to the underside of the floor or roof sheathing, slab or deck above or to the fire-resistance-rated floor/ceiling or roof/ceiling assembly above, and shall be securely attached thereto. If the partitions are not continuous to the sheathing, deck or slab, and where constructed of combustible construction, the space between the ceiling and the sheathing, deck or slab above shall be fire-blocked or draft-stopped in accordance with Sections 717.2 and 717.3 at the partition line. The supporting construction shall be protected to afford the required fire-resistance rating of the wall supported, except for tenant and sleeping unit separation walls and corridor walls in buildings of Types IIB, IIIB, and VB construction.CBC Section 708.9, Penetrations in a fire partition by ducts and air transfer openings shall comply with Section 716.Provide typical section view detail of all new partitions and ceilings showing: - Size, spacing, and material of framing members - Note gauge and ICC Research Report number and installation/construction requirements for metal framing members. - It is the project designer’s responsibility to coordinate work with the various trades to ensure that the size of the wall cavity will be large enough to accommodate piping, fittings, ducts, etc. There has been a continuing field problem of 2½” wide metal studs not being able to accommodate plumbing pipes. - Method of attaching framing to the building structure. Compliance shall be shown with CBC Section 1607.13 for lateral support of the walls. Do not support top of walls to suspended ceiling system unless calculations and drawing prepared by a registered engineer are submitted for review. Submit structural engineering calculations for walls in rooms with a floor to building structure above height greater than 14’. - Provide on the drawings details for the lateral support of partitions, rails and similar space dividers less than 5’ 9” in height. - Sheathing material and details of attachment. Note type, size, and spacing of fasteners. - Heights of partition, suspended ceiling, structure above. - Reference each fire-resistive assembly to a CBC Chapter 7 Table and Item number. - Fire-blocks and draft-stops in combustible construction in accordance with CBC Section 717. Show location(s) and provide typical construction details. - Fire/smoke damper locations, installation requirements and required access doors. Refer to CBC Section 716 and mechanical Code Section 606.EGRESSCBC Section 1004.3, Posting of occupant load. Every room or space that is assembly occupancy shall have the occupant load of the room or space posted in a conspicuous place, near the main exit or exit access doorway from the room or space. Posted signs shall be of an approved legible permanent design and shall be maintained by the owner or authorized agent.Revise occupant load calculation. Occupant load is calculated as follows: - Copy room #112: 150 Persons /SF. - Conference Room#113: 15 Persons / SF. - Library Room #116: 150 PersonsSheet A1.6. Egress sizing, The capacity, in inches, of means of egress stairways shall be calculated by multiplying the occupant load served by such stairways by a means of egress capacity factor of 0.3 inch per occupant and other than stairway shall use capacity factor of 0.2 inch per occupant.It appears the existing corridor has been removed on the new design. Revise design toprovide fire rated corridor or provide code analysis demonstrating that building comply with all requirements of current code in order to de- rate the existing corridor. (CEBC 301.3, 314.1, 503.1; CBC 909.6.3, 909.20, 1006, 1017, 1020; CFC 909.21)Revise egress route that egress from B occupancy to S or F occupancy is prohibited. (1016)The exterior egress door shall comply with CBC 1010. The roll-up egress door does not comply. Revise egress plan in shop area that designated egress route, travel distance, common path of travel, signage not egress through any roll-up doors.Two means of egress are required from the 2nd floor/mezzanine level due to the common path of travel exceeds 75 feet (80 feet measured on plan) per CBC Table 1006.2.1 and Table 1006.3.3 (2). Revise plan.In shop and warehouse room, separation of exits must comply with CBC Section 1007.2.1. A minimum of 46 feet is required between exit doors. (90 feet diagonal distance) Show justification on plan.Justify the egress travel distance and common path of travel at the remotest point in room 125 to exit doors. Egress from a room or space shall not pass through adjoining or intervening rooms or areas, except where such adjoining rooms or areas are accessory to the area served, are not a high hazard occupancy and provide a discernible path of egress travel to an exit.CORRIDOROn the first floor office area, egress through intervening space is not permitted. An option is to provide corridor with fire-resistance rated in accordance with Table 1020.1. The corridor walls required to be fire-resistance rated shall comply with Section 708 for fire partitions.Table 1020.1 Corridor Fire Resistance Rating: OccupancyOccupant LoadRequired Fire-Resistance Rating (Hours)Served By CorridorWithout sprinklerWith sprinklersystemsystem H-1, H-2, H-3, LAllNot Permitted1 H-4, H-5Greater than 30Not Permitted1 A, B, F, M, S, UGreater than 3010CBC Section 1020.2, Corridor width. The minimum corridor width shall be as determined in Section 1005.1, but not less than 44” (Min 48” per 11B-404).CBC Section 1017.4.1, Corridor ceiling. Use of the space between the corridor ceiling and the floor or roof structure above as a return air plenum is not permitted. See CBC Section 1017.4 for exceptions.CBC Section 1017.5, Corridor continuity. Fire-resistance-rated corridors shall be continuous from the point of entry to an exit, and shall not be interrupted by intervening rooms. E.g. provide separation between breakroom and hallways to have a continuous corridor to hallway #109.Foyers, lobbies or reception rooms constructed as required for corridors shall not be construed as intervening rooms. [SFM]CBC Section 1020.5, Air movement in corridors. Corridors shall not serve as supply, return, exhaust, relief or ventilation air ducts when required to be fire-resistive rated in accordance with Table 1020.1.Provide a complete architectural section of 1-HR. corridor detailing fire resistive rated construction of the walls and ceilings. Detail all duct and other penetrations CBC Sections 708.4, 1020.1, 716.1, Table 716.1(2) & 717.5.4.CBC Section 716.3.2. Where corridor walls are required to be one-hour fire-resistive construction by Section 1020, windows shall be protected by fixed glazing listed and labeled for a fire-protection rating of at least three-fourths hour in accordance with Section 716.3. The total area of windows in any portion of an interior corridor shall not exceed 25 percent of the area of the corridor wall of the room which it is separating from the corridor.CBC Section 716.2.2. When corridor walls are required to be of one-hour fire-resistive construction by Section 1020, every interior door opening shall be protected by a tight-fitting smoke-and-draft-control assembly having a fire-protection rating of not less than 20 minutes. Viewport in 20-minute rated door limited to 1” in diameter. Said doors shall not have louvers. The door and frame shall bear an approved label or other identification showing the rating, thereof, followed by the letter “s,” the name of the manufacturer, and the identification of the service conducting the inspection of materials and workmanship at the factory during fabrication and assembly, in accordance with NFPA 80 and UL 1784. Doors shall be maintained self-closing or shall be automatic closing by actuation of a smoke detector in accordance with Section 715.4.7. Smoke-and-draft-control door assemblies shall be provided with a gasket so installed as to provide a seal where the door meets the stop on both sides and across the top.Include the following notes with typical one-hour corridor section view: - Interior openings for other than doors or ducts shall be protected by fixed glazing listed and labeled for a fire protection rating of at least three-fourths hour in accordance with CBC Section 716.3. - Penetrations in fire-resistive walls shall comply with CBC Sections 716 and 717. - Cabinets such as recessed electrical panels, fire hose cabinets, and recess fire extinguisher cabinets constructed of steel are permitted, provided that the openings in the fire rated corridor are sealed with approved sealant material to prevent the passages of smoke. - Other cabinets should be installed or recessed so that there is no reduction in the fire rating of the wall, or opening which would allow smoke to pass. This would mean that the cabinet must be surrounded with material which provides the equivalent of one-hour fire resistance.Revise egress route DO NOT EGRESS from hallway #120 into warehouse room #125. Egress shall not pass through kitchens, storage rooms, closets or spaces used for similar purposes.EXIT SIGNSCBC Section 1013.1. Provide a directional exit sign at changes in exiting direction.CBC Section 1013, Requires exit signs to be readily visible from any direction of approach. No point shall be more than 100’ from the nearest visible exit sign. Revise the drawings to show compliance.CBC Section 1008, Requires means of egress from all occupied parts of the building be provided with at least 1’ candle of light at floor level. Show compliance on the drawings.Tactile exit signs shall be required at the following locations: - Each grade-level exterior exit door shall be identified by a tactile exit with the word “EXIT.” - Each exit door that leads directly to a grade-level exterior exit by means of a stairway or ramp shall be identified by a tactile exit sign with the following words as appropriate:“EXIT STAIR DOWN” - Each exit access door from an interior room or area to a corridor or hallway, which is required to have a visual exit sign, shall be For the purpose of Section 1013.4, the term “tactile exit signs” shall mean those required signs that comply with Chapter 11B, section 11B-703.1, 11B-703.2, 11B-703.3 or 11B-703.5. Provide detail. Notes alone will not be accepted.identified by a tactile exit sign with the words “EXIT ROUTE.”Sheet A7.00 Detail 3. Extensions of stairway handrails shall return to a wall, guard, or the landing surface, or shall be continuous to the handrail of an adjacent stair flight. §11B-505.10.PC2: Clearly show compliance on all handrail extensions on plan.EXIT DISCHARGECBC Sections 1028.5 and 1022.1. Exiting from shop and warehouse if to the rear site must be continuous, unobstructed, and undiminished to a public way. This includes gates within the fence which must show compliance with CDB Section 1010.2. Revise drawings to show compliance.Provide required exterior door landing at exterior side of the door on all exterior exit doors (exit door B, C E and F). There shall be surrounding the by the detectable warnings, minimum 36” wide, around required landing. At the emergency, maintain the clear path of egress on site from the exterior door not to be blocked by parked cars or other obstructions. Show required dimensions for landings, detectable warnings and details and how to maintain clear egress route on the site plan. (1010, 1028, 11B-247, 11B-705.1.2.5, 11B-404)ACCESSIBILITYWhen alterations or additions are made to existing buildings or facilities, an accessible path of travel to the specific area of alteration or addition shall be provided. Identify on the site plan the accessible path of travel from site arriving point (e.g. accessible parking) to the building main accessible entrance (CBC 11B-202.4)SITE ACCESSIBILITYRevise the accessible parking location from the rear of the building to the front. It shall be located on the shortest accessible route of travel from adjacent parking to an accessible entrance (as near as practical to an accessible entrance). (11B-208.3.1)An accessible route is required from accessible parking space to the front building accessible entrance. Show compliance of the accessible route on the site plan per 11B-402.(1) Van accessible parking space is required. Show dimensioned parking space on the site plan and cross-reference details. Details shall include required dimensions, access aisle, marking and signage. (11B-502)PC2: The required van accessible parking space shall not combined with any EV charging space. Provide separate Van accessible EV charging space.Near the front entrance, detectable warnings shall be provided to separate walks that cross or adjoin a route provided for vehicular traffic in a driveway, shall be 36 inches in width and continuous at the boundary between the pedestrian areas and vehicular areas. §202, §11B-247.1.2.5, §11B-705.1.2.5BUILDING ACCESSIBILITYThe main entrance door shall be accessible at the reception room (101). Show compliance on plan. (11B-404)PC2: Provide evidence on plan showing the existing main entrance door is accessible fully compliance with 2019 CBC if the existing main door is to remain. Add note or provide a diagram on plan to verify.Revise door #106 and #107 (2’-8” wide). Door openings shall provide a clear width of 32 inches minimum. Clear openings of doorways with swinging doors shall be measured between the face of the door and the stop, with the door open 90 degrees. Openings more than 24 inches deep shall provide a clear opening of 36 inches minimum. There shall be no projections into the required clear opening width lower than 34 inches above the finish floor or ground. Projections into the clear opening width between 34 inches and 80 inches above the finish floor or ground shall not exceed 4 inches. §11B-404.2.3Revise door #114. At least one of the active leaves of doorways with two leaves shall comply with 11B-404.2.3 (e.g. clear width of 32 inches) and 11B-404.2.4 Maneuvering Clearances. §11B-404.2.2Show on plan where the vertical clearance is less than 80” in height under the stairway space. Provide guard rail on plan and comply with CBC 11B-307.4. Vertical clearance below stairway shall be 80” high minimum.Door landings shall be 48” min in width on the hallway (push side) (11B-404).Breakroom area. Reduce counter height to 34” max to comply with side reach range requirement. (11B-308.3.2)Interior stairs shall have the upper approach and lower tread marked by a stripe providing clear visual contrast. Exterior stairs shall have the upper approach and all treads marked by a stripe providing clear visual contrast. The stripe shall be a minimum of 2 inches wide to a maximum of 4 inches wide placed parallel to, and not more than 1 inch from, the nose of the step or upper approach. The stripe shall extend the full width of the step or upper approach and shall be of material that is at least as slip resistant as the other treads of the stair. A painted stripe shall be acceptable. Grooves shall not be used to satisfy this requirement. §11B-504.4.1PC2: Sheet A7.00. Please incorporate this requirements into enlarged stair plan. Note on the drawing.SANITARY FACILITIESDrinking fountain(s) shall be provided in accordance with the California Plumbing Code (CPC) Section 415.0 and CPC Table 4-1.PC2:In CPC, the water dispenser is not recognized as an alternative of the drinking fountains in section CPC 415. Please revise design.No fewer than two drinking fountains shall be provided. When provided, one drinking fountain shall comply with 11B-602.1 through 11B-602.6, 11B-602.8 and 11B-602.9 and one drinking fountain shall comply with 11B-602.7 and 11B-602.9. §11B-211.2 (See exception) PC2: Not resolved.Where existing toilet rooms or bathing rooms (restroom #107 and #108) do not comply with 11B-603 Toilet and Bathing Rooms, directional signs indicating the location of the nearest compliant toilet room or bathing room within the facility shall be provided. Signs shall comply with 11B-703.5 Visual Characters and shall include the International Symbol of Accessibility complying with 11B-703.7.2.1 ISA. Where existing toilet rooms or bathing rooms do not comply with 11B-603 Toilet and Bathing Rooms, the toilet rooms or bathing rooms complying with 11B-603 Toilet and Bathing Rooms shall be identified by the International Symbol of Accessibility complying with 11B-703.7.2.1 ISA.Doorways leading to toilet rooms and bathing rooms shall be identified by a geometric symbol complying with 11B-703.7.2.6 Toilet and Bathing Facilities Geometric Symbols. The symbol shall be mounted at 58 inches minimum and 60 inches maximum above the finish floor or ground surface measured from the centerline of the symbol. Where a door is provided the symbol shall be mounted within 1 inch of the vertical centerline of the door. §11B-703.7.2.6PC2: On sheet A1.41, remove pictogram, text and braille on the door-mounting signs.Unisex toilet and bathing facilities shall be identified by a circle, ¼ inch thick and 12 inches in diameter with a ¼ inch thick triangle with a vertex pointing upward superimposed on the circle and within the 12-inch diameter. The triangle symbol shall contrast with the circle symbol, either light on a dark background or dark on a light background. The circle symbol shall contrast with the door, either light on a dark background or dark on a light background. §11B-703.7.2.6.3Relocate wall-mounted restroom signage (braille sign) from the restroom door to the wall on the latch side of the door. Provide 18”x18” clear space in front of the wall-mounted signage. Provide tactile exit signage and identify locations on floor plan (e.g. door-mounted restroom sign, tactile exit sign…). Include sign elevation and typical signage text per CBC Section 1013.1 at doors to exit passageways, exit discharge and exit stairways shall comply with CBC Sections 11B-703.1, 11B-703.2,11B-703.3, and 11B-703.5. (CBC 11B- 216.4.1) Tactile characters on signs shall be located 48” minimum above finish floor, measured from the baseline of the lowest Braille cells and 60” maximum above finish floor, measured from the base line of the highest line of the raised characters. (CBC 11B-703.4.1 & Figure 11B-703.4.1) Provide design and detail for shower folding seat (note #23, sheet A5.10) on plan to show compliance with 11B-608.4. The controls, faucets, and shower spray units shall be located on the back wall of the compartment adjacent to the seat wall 16” minimum and 27” maximum from the seat wall; and shall be located above the grab bar, but no higher than 48” above the shower floor. (11B-608.5.2) The space between the grab bar and walls/projecting objects shall be 1-1/2 inches minimum. (CBC 11B-604.5, 11B-609.3). PC2: Not resolved. Show requirements by notes or diagrams on plan.CALGREENUpdate sheet A1.50 to show compliance with 2019 California Green Building Standards Code, not 2020 LAGBC. Revise plan.Provide long-term bicycle parking on the site plan or floor plan. Show facility or enclosure comply with code requirement.Provide short-term bicycle parking on the site plan, located by the main entrance for guest use. (bike racks)ENERGYIf the office area is conditioned, provide energy design on plan for altering building envelope. Alll NRCC pages shall be incorporated on plan and signed by the responsible design professional.STRUCTURALProvide lateral support at the top and bottom of all non-load bearing walls which are not shown and prat of the submitted structural package.The structural plans include only partial of the TI area. A number of interior partitions are removed without identifying if any of those are structural walls. Please clarify on plan. Structural design is needed if removing any structural walls.PC2: Please clarify on plan. In addition, please refer to architectural demolition plan on sheet A3.01. E.g. please provide design and details on the new wall opening(s) on grid line 4.Sheet S1. Update the applicable code to 2019 version of CBC in the design criteria.Sheet S3. Specify the weight of the floor mounted “Gaylord pcu unit” (refer to arch. Sheet A3.10) on the plans. Provide engineering calculations and structural plans for the support and anchorage of the floor mounted equipment. On the floor plan, show anchorage detail and reinforcement of the framing and connections. [ASCE 7-16, Sections 13.1]Provide framing plan for new partitions at the mezzanine level and provide design and details the wall bracing to the bottom floor and to the roof framing.Lateral collector. Tying 4x10 beams to transfer lateral force to the shear wall on grid line A.NEW CORRECTIONS PER REVISED PLAN (2ND Submittal)ARCHITECTURAL COMMENTSRefer to sheet A3.10. Ground floor plan. The newly added (1) lavatory sink (note #14) and water dispenser (note #15) shall be accessible and shall NOT be encroached into the required egress route, accessible route and shall comply with protruding object requirement (11B-307). Please revise design. (CBC Ch10, Ch 11B)Alteration of the restroom #107 and #108 shall be fully accessible in compliance with CBC 11B Division 6. Please provide enlarged and dimensioned floor plan showing accessible plumbing fixtures, clearance, maneuvering space, doors, door swing, signage and etc…STRUCTRUALThe mezzanine level is changed to storage area per architectural plan. Please design heavier live load per CBC Table 1607.1 item #31 for either 250 psf or 125 psf live load. Per calculation, framing is only design to support 50 psf live load. Please coordinate with the architect for the proposed use and review structural design for new mezzanine deck framing, foundation and justify existing 2x8 floor joists.Update the design loads and other information pertinent to the structural design required by Sections 1603.1.1 through 1603.1.9 on the plans.END OF COMMENTS