HomeMy WebLinkAbout282355_2_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101108888
PROJECT ADDRESS:
1951 E Dyer Rd Unit# D
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B, SPK
OCCUPANCY CLASSIFICATION(S):
B, M
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
12/14/2021
INITIAL REVIEW
1/12/2022
EXPIRATION
6/12/2022
RECHECKS:
1.2/11/2022
PROJECT APPLICANT CONTACT PERSON:
2.
William Peters
3.
TEL:
(949)412-4428
FAX:
VALUATION: $35,000.00
EMAIL:
williamapeters@yahoo.com
FLOOD ZONE: X-0602320278J
APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)
- County of Orange Health Department approval on the corrected/final set of drawings ((714)433-6000)Sheet A-1: Floor Plan – Please provide Wall Legend to clearly identify existing (E), new wall (N), etc. Door to general storage room: Please relocate counter to provide minimum 18” clear from door strike edge, on the pull side. Door at hallway adjacent to general storage room: 60” maneuver space is required on the pull side of door. Please coordinate and revise plan accordingly. 2nd Review Comment: Door 6 – a 60” maneuver space is required on the pull side of door. Please coordinate and revise plan accordingly. Doors: on the plan, please provide door schedule, including door hardware. Doors: Please provide 48” maneuver space on the push side of door – show dimension on plan. 2nd Review Comment:Plan was not revised, please provide minimum 48” clear maneuver space on the push side of door, measured in the direction of travel. Reception counter: Please provide/show accessible counter with counter height of 34” maximum. 2nd Review Comment: Reminder – please transfer the “ink” handwritten / marked onto the electronic prior to printing. Revised elevation on sheet A-3 as related. Sheet A-1: Restroom Water Closet: a 60” floor clear space is required for the water closet. Please remove wall between water closet and sink to provide 60” clear floor space. 2nd Review Comment: Referenced detail 1/A-2 – Please revise restroom floor plan to show 60” clear floor space for the water closet (measured from the side wall to the edge of the vanity). On the plan, please provide construction detail for new wall. Details shall be clearly cross-reference onto the plan. 2nd Review Comment: Please provide the following information for the wall and ceiling construction Detail 5/A-2 – on the plan, please specify ICC report number for the metal studs and ramset anchor. Ceiling: Please provide ceiling plan to show ceiling finish, ceiling height, etc. Please provide ceiling framing plan and attachment details. ***PLAN WAS INCOMPLETE. PLAN REVIEW WILL CONTINUE AT TIME OF RESUBMITTAL ANDADDITIONAL COMMENT MAY BE REQUIRED***