PLAN CHECK NO:
102109859
PROJECT ADDRESS:
1019 N Euclid St Unit# 3
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3, U
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
3/22/2022
INITIAL REVIEW
4/5/2022
EXPIRATION
9/18/2022
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Leon Tran
3.
TEL:
(714)418-6604
FAX:
VALUATION: $35,000.00
EMAIL:
Trandesign7@gmail.com
FLOOD ZONE: A-0602320143J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
-Police Department approval on the corrected/final set of drawings (647-5840).
-Public Works Agency approval (647-5039).
Sheet A1:
Plan shall be stamped, signed and dated by the engineer of record. Apply to all sheets.
Site plan: For clarity, please note (specify) plan check number for each unit.
Site plan: Unit #2, 1019 N. Euclid Street – Please remove the ½ address.
Site plan: Please specify 1019, Unit #3 for the proposed ADU.
Site plan: 1021 N Euclid Street – Please remove/omit note indicated “Unit #3).
Proposed Information: Flood Zone – Please revise plan to specify Flood Zone ‘A’.
Sheet A2.2:
Proposed Flood Plan: For clarity, please show unit #2 and Unit #3 (ADU).
Wall separating two sleeping unit shall be constructed with a one-hour fire-rated wall. Please show on plan and provide construction detail. Details shall be clearly cross-referenced onto the plan.
The fire-rated wall shall be extended from floor/slab to the underside of the roof sheathing.
New window A at living room (for both units): Please provide tempered glass.
Please provide exhaust / hood in the kitchen area.
Please show/provide smoke alarm inside of each sleeping room, and outside at the area giving access of sleeping room.
Provide carbon monoxide alarm outside of each sleeping room.
Please provide/show attic access for both units.
Sheet A2.3:
Provide/show smoke and carbon monoxide alarm in accordance with Section R314 and R315.
Sheet A5:
Detail 1 and 2 on sheet A5: Roof insulation is not required in garage. Please revise details to omit the roof insulation.
Simpson Strong wall is provided – On the plan, please provide Strong Wall Standard detail sheets.
Framing plan: Please show 4x12 header continue over the Simpson Strong Wall.
(End of comment)