HomeMy WebLinkAbout284580_2_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101109545-46
PROJECT ADDRESS:
1700 E Carnegie Ave Unit# 125 & 225
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
III B, SPK
OCCUPANCY CLASSIFICATION(S):
B, S-1, F-1
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
3/3/2022
INITIAL REVIEW
3/13/2022
EXPIRATION
8/30/2022
RECHECKS:
1.4/30/2022
PROJECT APPLICANT CONTACT PERSON:
2.
Heather Shreve
3.
TEL:
(949)788-4033
FAX:
(949)660-9128
VALUATION: $718,600.00
EMAIL:
hshreve@waremalcomb.com
FLOOD ZONE: X-0602320278J
APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Fire Department approval on the corrected/final sets of drawings ((714)573-6100)
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)Sheet I0.1On the plan, provide summary for hazardous materials stored and used in the proposed building. The used and stored hazardous material shall not exceed the qualities set for in Table 453.7.2.1. (CBC 453)2nd Review Comment: Sheet I0.1b was not stamped and signed by the architect of record. Plans shall be stamped, signed, and dated by the architect of record. Storage and use of hazardous materials shall be also submit to Orange County Fire Authority (OCFA) for review. 2nd Review Comment: Occupancy group classification is pending OCFA review and approval of the hazardous material to be stored on the premise.Sheet I2.3: Please clearly identify Demising Wall between suites, including existing and new. 2nd Review Comment: The demising wall shall be a full height wall. Please revise plan and detail to show full height wall. Restrooms: On the plan, please show/provide accessible restrooms. Show restrooms in compliance with 11B-Division 6 for persons with disabilities. 2nd Review Comment: Referenced restroom details – Please update details to provide toilet dispenser located 7”-9” measured from the front edge of the water closet to the centerline of the dispenser. Mechanical, Electrical and Plumbing Plans: Mechanical, electrical and plumbing plans are not part of this plan review and approval. Please do NOT include the MEP sheets.