HomeMy WebLinkAbout289537_1_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101111040-41 PROJECT ADDRESS: 806 S Sycamore St PLAN CHECK ENGINEER: Le, TungTEL:714 647-5896 EMAIL: Tle10@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): R-3, U PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 6/30/2022 INITIAL REVIEW 7/11/2022 EXPIRATION 12/27/2022 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Eduardo Yepez 3. TEL: (951)858-0925 FAX: VALUATION: $5,382.00 EMAIL: eduardo@pgshomeandsolar.com FLOOD ZONE: X-0602320276J Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: -Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. - Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700). -Police Department approval on the corrected/final set of drawings (647-5840). -Public Works Agency approval (647-5039). - School District Compliance Certificate; and a copy of the building permit application, signed by the plan check engineer, shall be required by the School District to verify the scope of the work. Sheet 2, Detail 3: Revise detail to show concrete curb at the exterior wall where applicable. Sheet 3: Foundation: Please provide a footing detail for the existing footing. Provide details to show positive connection between the existing slab/footing and new slab/footing. Detail 1 on sheet 4: Please revise detail to show concrete curb (match with building section). Sheet 4: Please revise detail to show 2x4 wall studs (details 1, 2, 3, 6, 11, etc.). Sheet 6, City Standard: Please fill out the patio size, post size, post spacing, header size, rafter span, rafter size and spacing, lumber grade. Final plans shall be signed and dated by the person who is responsible for the construction plans. (End of Comment)