HomeMy WebLinkAbout289090_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101110898
PROJECT ADDRESS:
3 E MacArthur Pl Unit# 750
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
I A, SPK
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
6/29/2022
INITIAL REVIEW
7/10/2022
EXPIRATION
12/26/2022
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Matthew Snyder
3.
TEL:
(949)324-7131
FAX:
VALUATION: $500,000.00
EMAIL:
msnyder@LDCindustrial.com
FLOOD ZONE: X-0602320278J
APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)Sheet TI-A0.1: Mechanical, Plumbing, and Electrical: Please note “UNDER SEPARATE REVIEW”. Please correct suite number. Apply to all sheets. Site plan: Please provide a complete architectural site plan showing property lines, streets, north arrow, all buildings/structures located on the same lot. On the plan, please show/provide an accessible route from the public sidewalk to the building primary accessible entrance. Accessible route shall be 5% maximum slope, measured in the direction of travel, 2% cross-slope max, and 48” wide minimum. On the plan, please show accessible parking stalls with an accessible route to the building entrance. Provide details and clearly cross-reference details onto the plan. Show/provide detectable warning where required. Egress Plan: Please provide complete egress plan for the floor where alterations are occurred. Plan review will continue at time of resubmittal and additional comment may be required. Interior accessibility: Please show an accessible route from the building entrance to the altered area. Provide details to show existing elevators are accessible to the persons with disabilities. Provide/show accessible restrooms. Provide restroom floor plans and details to show compliance with Chapter 11B, Division 6. Details shall be clearly cross-referenced onto the plan so that it can be easily located. Plan review will continue at time of resubmittal and addition comment may be required. Sheet TI-A2.1: Demo plan: Existing columns projection must be remained (protected in place). Please revise demo plan and clearly provide the statement on the plan. Sheet A2.2: Please revise plan to show the new double-doors (A) to swing outward. Please clearly reference to sheet A5.1 for window and door schedule. Wall supporting window W1: Please provide construction detail for wall show attachment at top and bottom of wall. Referenced detail 4/TI-AD.2: Detail referenced to detail 17 for top wall bracing was insufficient. Please revise detail to show wall braced to structural floor/ceiling frames above. Structural CommentProvide structural calculation and details for support of glass wall panels and doors. Details shall be clearly cross-referenced onto the plan. (End of Comments)