HomeMy WebLinkAbout289697_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
103111092
PROJECT ADDRESS:
5110 Westminster Ave Unit# M
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
7/6/2022
INITIAL REVIEW
7/17/2022
EXPIRATION
1/2/2023
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Anthony D Chau
3.
TEL:
(714)768-3092
FAX:
VALUATION: $30,000.00
EMAIL:
ar.dchau@gmail.com
FLOOD ZONE: A-0602320143J
APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)Sheet A-0: Final plans shall be signed and dated by the designer. Apply to all sheets. On the plan, please show/provide an accessible path of travel from the public sidewalk to the building accessible primary entrance. Please show an accessible route from the accessible parking stall to the building entrance. On the plan, please provide detail of concrete curb and detectable warning. Details shall be clearly cross-referenced onto the plan. On the plan, please provide details for accessible parking stall and signage. Details shall be clearly cross-referenced onto the plan. Sheet A-1: Interior curved wall partition: Please show/provide access from the building entrance to the back of the building, including the restroom. Existing restroom shall be made accessible to persons with disabilities. Provide restroom floor plan with all the required dimensions per Chapter 11B, Division 6. Provide minimum 60” clear landing for restroom door on the pull side. Procedure stations: Please show/provide wheelchair space for person using wheelchair. Provide construction detail for the new curved wall. Provide supported details at top and bottom of wall. Common sink adjacent to the procedure stations: Sink shall be made accessible to persons with disabilities. Please provide details to show compliance with 11B-606. Sheet A-2: Provide details for ceiling finishing. Provide ceiling framings and details for ceiling finish. Provide details of receptacle outlets and lighting switch control per Section 11B-308. **PLAN WAS INCOMPLETE. PLAN REVIEW WILL CONTINUE AT TIME RESUBMITTAL. ADDITIONAL PLAN REVIEW COMMENTS AND PLAN CHECK FEE MAY BE REQUIRED. (End of Comment)