HomeMy WebLinkAbout286909_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101110242 PROJECT ADDRESS: 308 E Dyer Rd PLAN CHECK ENGINEER: So, AnsonTEL:714 647-5830 EMAIL: aso@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): F-1 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 4/27/2022 INITIAL REVIEW 6/6/2022 EXPIRATION 10/24/2022 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Rob Olson 3. TEL: (949)278-3933 FAX: VALUATION: $2,600.00 EMAIL: 1rwolson@gmail.com FLOOD ZONE: X-0602320278J APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5830 for an appointment.Sheet A-1Revise the occupancy group to F-1 under Code Review.Delete the following note under Code Review:” Occupancy Separate – One Hour”.Delete the following code reference under Code Review: CRC, CMC, CPC, CEC & 2020 California Energy Code.”Revise the Scope of Work:” Demolish 18 inches of concrete wall on each side of the door, and install a new door.”The dimensions on the floor plan does not match the structural calculations. The drawings on the structural calculations show a 16-foot opening with 1’-8” concrete wall on both sides of the opening. The architectural drawing shows a 17-foot opening with 1’-6” concrete wall on both sides of the opening.The Engineer On Record who provides the structural opinions shall stamp and sign the floor plan.[END]