HomeMy WebLinkAbout282510_4_Corrections.docxRESIDENTIAL PLAN CHECK
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
102108943
PROJECT ADDRESS:
2214 W Edna Dr
PLAN CHECK ENGINEER:
Ahangian, KathyTEL:714
647-5812
EMAIL:
Kahangian@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
R-3, U
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
12/16/2021
INITIAL REVIEW
12/29/2021
EXPIRATION
6/14/2022
RECHECKS:
1.2/27/22
PROJECT APPLICANT CONTACT PERSON:
2.
Roni Matar
3.
TEL:
(408)800-0008
FAX:
VALUATION: $40,000.00
EMAIL:
info@beirutech.com
FLOOD ZONE: X-0602320144J
Note: Numbers in parenthesis (unless otherwise noted) refer to code sections of the 2019 California Residential Code (CRC); 2019 California Building Code (CBC); CMC = 2019 California Mechanical Code; CPC = 2019 California Plumbing Code; CEC = 2019 California Electrical Code; T = Table; ICC = International Code Council.All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5812 for an appointment.The drawings/information submitted for Building Safety Division review is incomplete. The applicant shall, prior to resubmitting, complete all construction documents to show compliance with the 2019California Building Standards Code with local amendments and to clearly indicate the scope of work under this building permit application. There may be additional requirements when complete construction drawings and supporting data is submitted for Building Safety Division review.
Please see corrections on submitted plans. Red marked set must be returned with revised plans. Plans resubmitted without the red markup set may result in delayed review time and additional plancheck fees.
All drawings and supporting documents shall be prepared, stamped, and signed by a California licensed architect or registered professional engineer. (CRC R301.1.3, CBC 107.1 and 107.3.4.1).
This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647-5800 for information.
The applicant shall obtain clearances/approvals for the following, prior to building permit issuance:
-Planning Division approval on the corrected/final set of drawings (647-5804). Previously
approved plans should be submitted to expedite the process.
-Public Works Agency approval (647-5039).
- Proof of Worker's Compensation Insurance shall be required at the time of permit issuance.
Drawings must be to scale and be on 18" x 24" minimum sheets.( Please Clarify the scale)
Provide a fully dimensioned Site Plan on the drawings and on a separate 8-1/2" x 11" sheet of paper.
Provide building information on plans:(Pending 2/27/22)
- Occupancy type: R3 / U
- Construction type: Type V – B
Provide a statement on the title sheet of the plans that this project shall comply with following codes:( Pending 2/27/22)
- 2019 California Residential Code (CRC)
- 2019California Building Code (CBC)
- 2019 California Electrical Code (CEC)
- 2019 California Mechanical Code (CMC)
- 2019 California Plumbing Code (CPC)
- 2010 California Energy Code (CEnC)
- City of Santa Ana Municipal CodeShow location of heating equipment on the plans. (CRC R303.8)( pending2/27/22)All new construction, interior or exterior alterations, repairs, or additions requiring a permit and having a valuation in excess of $1,000, or when one or more sleeping rooms are added or created, the entire dwelling shall be provided with smoke detectors located as required for a new dwelling. (CRC R314.3) Smoke alarms shall be installed in the following locations: (Pending 2/27/22)
- In each sleeping room.
- Outside each separate sleeping area in the immediate vicinity of the bedrooms.
- On each additional story of the dwelling, including basements and habitable attics but not
including crawl spaces and uninhabitable attics. In dwellings or dwelling units with split
levels and without an intervening door between the adjacent levels, a smoke alarm
installed on the upper level shall suffice for the adjacent lower level provided that the lower
level is less than one full story below the upper level.
- When more than one smoke alarm is required to be installed within an individual dwelling
unit the alarm devices shall be interconnected in such a manner that the actuation of one
alarm will activate all of the alarms in the individual unit.All new construction, Interior or exterior alterations, repairs, or additions requiring a permit and having a valuation in excess of $1,000,, an approved carbon monoxide alarm shall be installed in dwelling units and in sleeping units within which fuel-burning appliances are installed and in dwelling units that have attached garages shall be provided with carbon monoxide alarms (CRC R315)( Pending 2/27/22)
- Carbon monoxide alarms shall only be required in the specific dwelling unit or sleeping unit for
which the permit was obtained. Carbon monoxide alarms required by Sections R315.1 and
R315.2 shall be installed in the following locations: ________.
- Outside of each separate dwelling unit sleeping area in the immediate vicinity of the bedroom(s).
- On every level of a dwelling unit including basements.
- Where more than one carbon monoxide alarm is required to be installed within the dwelling unit or
within a sleeping unit the alarm shall be interconnected in a manner that activation of one alarm
shall activate all of the alarms in the individual unit.Glazing in swinging, sliding, and bifold doors 9 square feet or less shall be a minimum category classification of I (CPSC 16 CFR 1201) and II (CPSC 16 CFR 1201) when more than 9 square feet or sliding. (Table R308.3.1 (1), R308.3 (1)) ( For folding door)(Pending 2/27/22)Glazing in door and enclosures for hot tubs, whirlpools, saunas, steam rooms, bathrooms, showers less than 5’ above the standing surface shall have a minimum category classification of II (CPSC 16 CFR 1201). (CRC TR308.3.1 (1) & 308.4(5)) (Pending 2/27/22)Doors between the garage and private residence shall be self-closing and self-latching and smoke proof.(CRC R302.5.1) (Pending 2/27/22) Provide landing at the entire length of the new sliding door.(Pending 2/27/22) Provide size and type of new sliding door in the living door and show it is tempered.(Pending 2/27/22) Show window # 8 and #3 are tempered.(Pending 2/27/22)Indicate all compliance measures from the energy compliance documentation on the plans. (i.e., Insulation for sections, U-factors SHGC). Revise door and window schedule or floor plans to show compliance. ( Show new windows and folding door comply with CEC 2019)(Pending 2/27/22)Provide complete framing plan for the front entry and engineering calculation to justify new openings. ( Lateral and vertical)Provide engineering calculation and construction detail for enlarging patio door in the living room.((Justify lateral and vertical)Please fillout attached SB-407 and copy it on the drawings.( Not found2/27/22) 2/27/22Please note ; Grid line (D) on sheet S2, doesn’t exist since the sun room is unpermitted and shall be removed.Line ( E ) is not a shearwall, which shear wall it is representing.Please show exact location of the grid lines, looks like there is a typo and grid lines are misaligned. Show exact location of grid lines.Please show all existing shear walls on the drawings to be able calculate the tributary area, please justify removal of the solid wall at the front door.Please see all the redmarks on the drawings and make sure the comments and the red marks are responded. ( PLEASE DO NOT RESUBMIT DRAWINGS BEFORE RESPONDING TO ALL THE COMMENTS)