HomeMy WebLinkAbout291095_2_Corrections.docxPLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101111511
PROJECT ADDRESS:
3511 W Sunflower Ave
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B, SPK
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
8/2/2022
INITIAL REVIEW
8/26/2022
EXPIRATION
1/29/2023
RECHECKS:
1.10/4/2022
PROJECT APPLICANT CONTACT PERSON:
2.
Joseph Hernandez
3.
TEL:
(626)710-8306
FAX:
VALUATION: $30,000.00
EMAIL:
projectdox@dcexpediting.com
FLOOD ZONE: X-0602320258J
APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)Sheet A001: Project Data: There was no permit record that show occupancy group A-3 for the existing building. Please coordinate and revise occupancy groups accordingly. 2nd Review Comment:Breakroom may classify as A-2 occupancy where food and drinks are consumed. Please coordinate and revise plan accordingly. Sheet A101: On the plan, please show location of existing curb ramps and detectable warning along the accessible route. 2nd Review Comment: Please provide detail for concrete curb ramps. Detail must be site specific and clearly cross-referenced onto the plan. Provide detail of existing and new curb ramps to show compliance with 11B-406. Details shall be clearly cross-referenced onto the plan. 2nd Review Comment: Please provide detail showing complying with Section 11B-406. Detail shall be clearly cross-reference onto the plan. Detail 2: Please clearly show walkway adjacent to the accessible parking stalls, including curb ramps and detectable warning. 2nd Review Comment: Detail 2/A008 called out on the enlarged details was not applicable. Please coordinate and revise plan accordingly. Accessible parking stall: Please provide required information for accessible parking. Details shall be clearly cross-reference onto the plan. 2nd Review Comment: Detail 1/A014 callout for accessible parking stalls was not applicable. Please coordinate and revise detail accordingly. EVvan accessible vehicle space: Please provide detail for EV van accessible parking stall with marking and identification signs per 11B-812.6. The blue color required for identification of access aisle for accessible parking shall not be used. The international wheelchair symbol marking is not required on the vehicle space. 2nd Review Comment: Response was incomplete nor plan was not revised. The comment above remain applicable. Detail 6: Please clearly show the reach range measured from the walking surface to the operable features. Show walking surface or finish surface. (11B-308)2nd Review Comment: Response was incomplete nor plan was not revised. The comment above remain applicable.(End of Comment)