HomeMy WebLinkAbout290380_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101111306 PROJECT ADDRESS: 2727 S Susan St PLAN CHECK ENGINEER: Le, TungTEL:714 647-5896 EMAIL: Tle10@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: III B, SPK OCCUPANCY CLASSIFICATION(S): B, F-1, S-1 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 7/21/2022 INITIAL REVIEW 8/8/2022 EXPIRATION 1/17/2023 RECHECKS: 1.10/18/22 PROJECT APPLICANT CONTACT PERSON: 2. VERONIKA FERNANDEZ 3. TEL: (929)999-6279 FAX: VALUATION: EMAIL: VFERNANDEZ@BAM-STUDIO.COM FLOOD ZONE: X-0602320258J APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Fire Department approval on the corrected/final sets of drawings ((714)573-6100)Sheet A-102: Gate shall be accessible to persons with disabilities. Show 10” smooth surface at the bottom of gate on the push side. Provide gate hardware information. Egress doors/gates shall be readily openable from the egress side without the use of a key or special knowledge or effort. (1010.1.9) Openable parts of such hardware shall be 34 inches minimum and 44 inches maximum above the finish floor or ground. The force for pushing or pulling open a door shall be 5-lb maximum. Operable parts shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist.Revise plan to provide 24” clear from the door strike edge on the pull side of gate. 2nd Review Comment: In addition to the provided note 1.35, please provide elevation of the gate with the required information. Sheet A-103: Exterior Area 2 – elevation: Stairway handrails – please revise handrail to show handrail along the stairway be continuous with no obstruction. (see markup plan)2nd Review Comment: Handrails are at 34”-38” height and guardrails are at 42” height – Please coordinate and revise elevation to show 34”-38” height guardrails with horizontal extension, and 42” height guardrails. Structural Review Comment: Provide structural calculation and details for the fencing and gate supports, including structural material notes and specification. 2nd Review Comment: Please provide structural details for the fencing on the plan. Show post size, spacing of posts, footing details, etc. (End of Comment)