HomeMy WebLinkAbout293277_5_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101112183 PROJECT ADDRESS: 1900 E Warner Ave Unit# E PLAN CHECK ENGINEER: Ahangian, KathyTEL:714 647-5812 EMAIL: Kahangian@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): S-1 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 9/28/2022 INITIAL REVIEW 10/9/2022 EXPIRATION 3/27/2023 RECHECKS: 1.10/22/22 PROJECT APPLICANT CONTACT PERSON: 2. Sean Maddocks 3. TEL: (949)291-0587 FAX: VALUATION: $50,000.00 EMAIL: Maddocks@greencp.com FLOOD ZONE: X-0602320279J APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5812 for an appointment.Please return marked up set of drawings with corrections.The drawings/information submitted for Building Safety Division review is incomplete. The applicant shall, prior to resubmitting, complete all construction documents to show compliance with the 2019 California Building Standards Code with local amendments.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Fire Department approval on the corrected/final sets of drawings ((714)573-6100) - Police Department approval on the corrected/final set of drawings (647-5840) - Public Works Agency approval (647-5039) - Orange County Sanitation District (714) 593-5756 - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceProvide the following:Pending10/22/22 Enlarge path of travel , parking, ramp, curb ramp,…to show compliance with accessibility. - Disabled access compliance must be shown on the site plan.Show on the plans: Ok 10/22/22 - Occupancy Classification(s) ( Type B & S1) - Type of Construction Sheet A8 is not provided. ( referenced on sheet A2) ok 10/22/22Provide typical section view detail of all new partitions and ceilings showing:pending 10/22/22 Provide minimum 24” oc shot pins on detail 4/A8. - Size, spacing, and material of framing members - Note gauge and ICC Research Report number and installation/construction requirements for metal framing members. - Method of attaching framing to the building structure. Compliance shall be shown with CBC Section 1607.13 for lateral support of the walls. Do not support top of walls to suspended ceiling system unless calculations and drawing prepared by a registered engineer are submitted for review. Submit structural engineering calculations for walls in rooms with a floor to building structure above height greater than 14’. - Sheathing material and details of attachment. Note type, size, and spacing of fasteners. - Heights of partition, suspended ceiling, structure above.Complete all soffit and furred out wall details. Provide complete detailing, including number, type, location of fasteners and how attachment is made to the building structure. Show compliance with CBC Section 803. ( If there is any alteration to the ceiling) ok 10/22/22 Show all the exit doors on the site plan. Pending 10/22/22, show on the site plan for unit E. Exits cannot go through storage room, relocate exit sign.Pending 10/22/22CBC Section 1022.1, Exit continuity. Exits shall be continuous from the point of entry into the exit to the exit discharge. Pending 10/22/22CBC Sections 1002 and 1028, EXIT DISCHARGE. That portion of a means of egress system between the termination of an exit and a public way. ( For the doors in the back) Pending 10/22/22CBC Section 1028.5, Access to a public way. The exit discharge shall provide a direct and unobstructed access to a public way.Pending 10/22/22Provide on the drawings a complete door schedule, showing:( For all the doors) pending 10/22/22For Existing doors to include entry doors. - Door sizes (CBC Sections 11B-404) - Hardware complying with exiting and disabled accessibility requirements The width of the level area on the side to which the door swings shall extend 24” past the strike edge of the door for exterior doors and 18” past the edgefor interior door. ( for the bathroom door)ok 10/22/22 Bathroom door on sheet A2.1 shows swing out and the floor plan shows swing in. Please clarify. Ok 10/22/22Show minimum 60” landing at the bathroom door. The door swings change ,pending 10/22/22 please show 60” at the swing side of the door. Show minimum 48 “ landing at the front of bathroom door.Not found 10/22/22Provide 60” clearance between toilet wall and the sink.Not Found 10/22/22Provide proper landing at the enclosed mezzanine door. Door opening onto a landing shall not reduce the landing to less than one-half the required width. CBC 1011.6.ok 10/22/22CBC Section 11B-404.2.7, Hand-activated door opening hardware shall be centered between 30” and 44” above the floor. Latching and locking doors that are hand activated and which are in a path of travel shall be operable with a single effort by lever-type hardware, by panic bars, push-pull activating bars, or other hardware designed to provide passage without requiring the ability to grasp the opening hardware. Locked exit doors shall operate as above in egress direction.Ok 10/22/22CBC Section 11B-404.2.9, Note on the drawings: “Maximum effort to operate doors shall not exceed 5 pounds for exterior doors and interior doors, such pull or push effort being applied at right angles to hinged doors and at the center place of sliding or folding doors. Compensating devices or automatic door operators may be utilized to meet the above standards. When fire doors are required, the maximum effort to operate the door may be increased to the minimum allowable by the appropriate administrative authority, not to exceed 15 pounds. Ok 10/22/22Stairways shall show compliance with CBC Sections 1009 and 1133B.4 including applicable disabled accessibility requirements. Ok 10/22/22 - Provide complete architectural plan view, sections, details, and notes for stairway(s). - Dimension stairway width showing compliance with CBC Sections 1009.1, 1005, and 1007.3. - Dimension rise of steps shall be not less than 4” or greater than 7”. The run shall notbe less than 11”.Provide proper landing at the enclosed mezzanine door. Door opening onto a landing shall not reduce the landing to less than one half of the required width. ( CBC 1011.6) ok 10/22/22CBC Section 11B-504, The upper approach and the lower tread of each interior stair shall be marked by a strip of clearly contrasting color at least 2” wide placed parallel to and close to (not more than 1” from) the nose of the step or landing to alert the visually impaired. The strip shall be of material that is at least as slip-resistant as the other treads of the stairs.Not found 10/22/22Provide handrail details on the drawings showing compliance with CBC Section 1009.10, 1012, and 11B-403.6.ok 10/22/22 - Stairways shall have handrails on each side. - Handrails shall be 34 to 38” above the nosing of treads. - Handrails shall extend a minimum of 12” beyond the top nosing, and shall extend a minimum of 12” plus the tread width beyond the bottom nosing. - Ends of handrails shall be returned or shall terminate in newel posts of safety terminals. - Handrails projecting from a wall shall have a space of 1½” between the wall and the handrail. The top of the guards shall not be less than 42” in height. Ok 10/22/22Tactile exit signs shall be required at the following locations: ok 10/22/22 - Each grade-level exterior exit door shall be identified by a tactile exit with the word “EXIT.” - Each exit door that leads directly to a grade-level exterior exit by means of an exit enclosure, or an exit passageway, shall be identified by a tactile exit sign with the words “EXIT ROUTE.” - Each exit door through a horizontal exit shall be identified by a sign with the words “TO EXIT.”It is the project designer’s/property owner’s responsibility to show compliance on the drawings with all applicable Federal and State Accessibility Standards.Ok 10/22/22 Drawings submitted to the Building Division for review shall provide the following information to insure compliance with CBC Section 11B-202.4: - An accessible entrancePending 10/22/22 - An accessible route to the altered areapending 10/22/22 - Accessible restroomspending 10/22/22 - Accessible telephone (if any) - Accessible drinking fountains, and - Parking, signage and alarmspending 10/22/22If a walk crosses or adjoins a vehicular way, and the walking surfaces are not separated by curbs, railings or other elements between the pedestrian areas and vehicular areas, the boundary between the areas shall be defined by a continuous detectable warning which is 36” wide, complying with the CBC Section 11B-247.1.2.5.pending 10/22/22Each lot or parking structure where parking is provided for the public as clients, guest or employees, shall provide accessible parking as required by CBC Section 1129B.pending 10/22/22CBC Section 1129B.3, Item 2. One in every eight accessible spaces, but not less than one, shall be served by an access aisle 8’-0” (96”) wide minimum and shall be designated van accessible as required by Section 1129B.4. The words NO PARKING shall be painted on the ground within each eight’ loading and unloading access aisle. This notice shall be painted in white letters no less than 12” high and located so that it is visible to traffic enforcement officialsnot found 10/22/22Complete the attached Disabled Accessibility Documentation Form.Pending 10/22/22 Provide accessibility upgrade up to $10,000 , bathrooms, path of travel, parkings ,….Provide Ceiling plan to show T-bar ceiling and any other altered ceiling. Ok 10/22/22 Please clarify if the new storage has any ceiling or it is open to the structure above. Ok 10/22/22Provide complete structural calculations and drawings for suspended ceiling systems showing compliance with CBC Sections 711.3.1, 803.9, 1613, and 1705 (special inspections) and ASTM C635 and ASTM C636. Ok 10/22/22Provide a complete suspended ceiling system plan and section detail showing the following:- Vertical supportsProvide attachment detail to the structure above. Pending 10/22/22 - Seismic wires - Seismic strut/Compression strut - Perimeter wires - Separate fixture wires for lights and mechanical devices - ICC Research Report number for the suspended ceilingSheet A3 shows enclosing existing mezzanine and converting into storage. Please provide calculation and construction detail to justify floor live load for a storage room.Pending , provide calculation. 10/22/22Show minimum 18” clearance to the strike edge of door from operation rooms #1 to loading /unloading. 10/22/22