HomeMy WebLinkAbout296846_1_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101113360 PROJECT ADDRESS: 1601 W Seventeenth St Unit# F-2 PLAN CHECK ENGINEER: Huang, GaryTEL:714 647-5862 EMAIL: Ghuang@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): B PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 12/30/2022 INITIAL REVIEW 2/6/2023 EXPIRATION 6/28/2023 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Fredrick Crooks 3. TEL: (714)235-6677 FAX: VALUATION: $190,000.00 EMAIL: fcrooks@fran-inc.com FLOOD ZONE: X-0602320144J GUIDELINES: Comments contained within this report reflect only those of the Building and Safety Division. Additional comments or corrective action may be required by other Departments and/or outside Agencies This Plan Review Report and all subsequent code references are based upon the most recent version(s) of the 2019 California Building Codes (CBC, CRC, CFC, CEC, CPC, CMC, CGBSC, and CEES) The approval of plans and any supporting documents does not permit the violation of any section of the adopted building codes or other pertinent local ordinances, or state and federal laws All listed plan review comments must be adequately addressed before a building permit can be issued Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used. Please see correction on submitted plans. Red marked set must be returned with revised plans. Plans resubmitted without the red markup set may result in delayed review time and additional plan check fees. PLAN REVIEW COMMENTS: Applicant shall address all the checked‘☒’ correction comments below before resubmitting plans to Building Safety for recheck. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: ☒Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. ☒Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700). ☒Police Department approval on the corrected/final set of drawings (647-5840). ☒Public Works Agency approval (647-5039). ☐Proof of Worker's Compensation Insurance shall be required at the time of permit issuance. ☐School District Approval; and a copy of the school fee worksheet, completed by the plan check engineer, shall be required by the School District to verify the scope of the work. ☐Grading Permit. Application is made through the Building Safety Division (647-5800) and the plan review is by the Public Works Agency (647-5039). ☒County of Orange Health Department approval on the corrected/final set of drawings (714)433-6000)This review does not include mechanical, plumbing or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, and electrical work. Call 647- 5800 for information.Cover Sheet: Path of travel shall be measured from the most remoted point of a roomSheet A2.0: Dimension to the all gender restroom shall match detail 1/A4.0Provide door type at the entrance to the prep room Provide minimum 44” clearance at the prep room Indicate minimum 18” maneuvering clearance at the entrance to the prep room Tempered glass is required at the storefront door Sheet A2.1, detail 4: provide maximum condensing unit equipment curb height Sheet A2.2, detail 1: provide smooth surface on the push side of the entrance door per CBC 11B-404.2.10 Sheet A4.0, detail 12: verify ICBO or LARR report number (End of Comment)