Loading...
HomeMy WebLinkAbout295768_2_Corrections.docxSPC PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101112987 PROJECT ADDRESS: 2350 S Redhill Ave Bldg# P PLAN CHECK ENGINEER: Lee, WayneTEL:714 647-5848 EMAIL: wlee@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: I B, SPK OCCUPANCY CLASSIFICATION(S): A-3, S-2 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 12/15/2022 INITIAL REVIEW 12/29/2022 EXPIRATION 6/13/2023 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Steven Finkelberg 3. TEL: (949)533-6852 FAX: VALUATION:$10,000.00 EMAIL: steven.finkelberg@greystar.com FLOOD ZONE:X-0602320279J APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTSPlease indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.All drawings and supporting documents shall be prepared, stamped and signed by a California licensed This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. - Fire Department approval on the corrected/final sets of drawings ((714) 573-6100).Resubmit plans. Please increase the size of plans to match the scale shown on the drawings (e.g. GS2.7A) and increase text height on plan to be legible.On next submittal, remove all electrical sheets from building plan review set, except the equipment specification for reference.Provide the narrative of the description of the scope on the first sheet of the building plan review set.Provide structural calculation to design and verify the equipment anchorage to the concrete slab as shown in detail 21/GS1.8. [ASCE 7-16, Sections 13.1]Cross-reference detail 21/GS1.8 into the applied location on sheet GS2.7A with clouds to indicate the scope of work area.Cloud the area on plan to show the extent of the scope under this generator permit on all sheets. END OF COMMENTS