HomeMy WebLinkAbout296743_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101113303 PROJECT ADDRESS: 110 S Center St PLAN CHECK ENGINEER: Lo, JonathanTEL:714 647-5822 EMAIL: Jlo@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: N/A OCCUPANCY CLASSIFICATION(S): N/A PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 12/28/2022 INITIAL REVIEW 1/11/2023 EXPIRATION 6/26/2023 RECHECKS: 1.2/1/2023 PROJECT APPLICANT CONTACT PERSON: 2. Ali Haddad 3. TEL: (657)223-6828 FAX: VALUATION: $50,000.00 EMAIL: ali@prosperarch.com FLOOD ZONE: X-0602320257J APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5822 for an appointment. 5. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance (CHECKED BOXES REQUIRED ONLY): ☒Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. ☒Public Works Agency approval (647-5039). ☐Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700). ☒Police Department approval on the corrected/final set of drawings (647-5840). ☐School District Approval; and a copy of the school fee worksheet, completed by the plan check engineer, shall be required by the School District to verify the scope of the work. ☐Proof of Worker's Compensation Insurance shall be required at the time of permit issuance. ☐Grading Permit. Application is made through the Building Safety Division (647-5800) and the plan review is by the Public Works Agency (647-5039).Comments have been provided on drawing and calculation hard copies in relation to all comments below. These may be picked up at Building and Planning department at applicants’ discretion.DrawingsSheet A0.1Proposed ADA parking spot and accessible aisle is not in an acceptable location. Spot and Aisle cannot be in driveway area or have potential cars backing/entering into area. Please relocate and ensure safe parking and aisle accessibility.PC #2: ADA access aisle is required to be 8’-0” min for 9’-0” van accessible spot. Revise width.PC #2: Show truncated dome on plan at existing curb where required. If existing curb is elevated, provide at ramp to parking lot. Trash Enclosure:Deck information not found on plans, provide type, gage, connections, etc…PC #2: Please provide justification for 2’-6” deck cantilever shown on plan.PC #2: Deck slope is not found, please provide.Provide gate pipes connections and foundation informationHSS member sizes not found on plans, provide sizes to match calculation design.Provide all HSS connections including HSS to HSS and HSS to baseplate. Provide welding notes as needed.CMU wall rebar does not match calculations, revise to match or redesign. CMU wall foundation does not match calculations, revise to match and ensure all information is provided.PC #2: Transfer rebar shown in 1/SD-2 information not found on plan. Please provide. Verify HSS Column note max @ 4’, is this a spacing or height maximum. Note is unclear.Provide HSS grade and wood grade notes for new material.Trash enclosure design shall be stamped and signed by EOR. Either on sheet or where information is provided. CalculationsProvide (2) sets of calculations for resubmittal review.(End of Comment)