HomeMy WebLinkAbout298399_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101113866 PROJECT ADDRESS: 1851 E First St Unit# 445 PLAN CHECK ENGINEER: Ahangian, KathyTEL:714 647-5812 EMAIL: Kahangian@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: I A, SPK OCCUPANCY CLASSIFICATION(S): B PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 2/14/2023 INITIAL REVIEW 2/18/2023 EXPIRATION 8/13/2023 RECHECKS: 1. 3/10/23 PROJECT APPLICANT CONTACT PERSON: 2. Lizzy Cadwell 3. TEL: (949)724-1499 FAX: VALUATION: $84,205.74 EMAIL: lizzy@spaces-oc.com FLOOD ZONE: X-0602320277J APPLICABLE CODE: 2022 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5812 for an appointment.Please return marked up set of drawings with corrections.Clearly indicate the scope of work under this building permit application:ok 3/10/23 - Revise project job description on the cover sheet to reflect creating suite 445 from 440.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Police Department approval on the corrected/final set of drawings (647-5840) - Public Works Agency approval (647-5039) - Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceProvide on the drawings a complete door schedule, showing: ( For all door) ok 3/10/23 - Door sizesNote on drawing: “Exit doors shall be openable from the inside without the use of a key or any special knowledge or effort.”( for breakroom door) pending 3/10/23, For shared breakroom, provide access from the common area.Each suite have access to the other suite?pending 3/10/23, For shared breakroom, provide access from the common area.Tactile exit signs shall be required at the following locations: (For suite 440)ok 3/10/23 - Each grade-level exterior exit door shall be identified by a tactile exit with the word “EXIT.” - Each exit door that leads directly to a grade-level exterior exit by means of an exit enclosure, or an exit passageway, shall be identified by a tactile exit sign with the words “EXIT ROUTE.” - Each exit door through a horizontal exit shall be identified by a sign with the words “TO EXIT.”Provide minimum 60” landing at the room # 1and #2of suite 440. ( Sheet A-1)Ok 3/10/23Complete the attached Disabled Accessibility Documentation Form.Pending 3/8/23, still is required.Provide minimum 48” landing at the conference room door. ( Sheet EG-1)Ok 3/10/23 Provide 12” clearance to the strike edge of breakroom door.Ok 3/10/23Provide elevation for the sink in the breakroom to show compliance with accessibility.Ok 3/10/23Please clarify if T-bar ceiling is new or existing? For new T-bar provide detail to show how it is attached to the structure above.Ok 3/10/23Detail 4/A5, please show how lower wall supported laterally.Ok 3/10/23