HomeMy WebLinkAbout298671_2_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101113970
PROJECT ADDRESS:
2100 S Susan St
PLAN CHECK ENGINEER:
Ahangian, KathyTEL:714
647-5812
EMAIL:
Kahangian@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B, SPK
OCCUPANCY CLASSIFICATION(S):
B, F-1, S-1
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
2/21/2023
INITIAL REVIEW
3/20/2023
EXPIRATION
8/20/2023
RECHECKS:
1.4/7/23
PROJECT APPLICANT CONTACT PERSON:
2.
Kendra Minkler
3.
TEL:
(818)271-7080
FAX:
VALUATION: $150,000.00
EMAIL:
kminkler@falconbrands.com
FLOOD ZONE: X-0602320258J
APPLICABLE CODE: 2022 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.Meetings between the project applicant/designer and the plan reviewer shall be by appointment only. Please call (714) 647-5812 for an appointment.Please return marked up set of drawings with corrections.This review does not include mechanical, plumbing, fire sprinkler system, or electrical work. Separate plans, applications, fees, plan checks, and permits are required for mechanical, plumbing, fire sprinkler systems, and electrical work. Call 647-5800 for information.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Public Works Agency approval (647-5039). ( For new sink)
- Proof of Worker’s Compensation Insurance shall be required at the time of permit issuanceApplication shows, framing of 1 overhead door. Unable to find it on the drawings Please clarify on the drawings, or revise application to match the construction detail.Pending 4/7/23, unable to find please cloud it on the drawings.Show new sink in the breakroom complies with accessibility.Pending 4/7/23 please show elevation and the knee space. Provide exiting plan from Vegetation room and dry room. ( maximum common path of travel is 100 feet)Pending 4/7/23 please see common path of travel distance ( Red mark) on sheet A3, it is over 100 feet from each room.Provide clearance to the all columns on sheet A2. ( please see red marks)Ok 4/7/23Show 18” clearance to the strike edge of bathroom 105 door.Ok 4/7/23Red marks and correction list will be available for pick up at the permit counter, Monday- Thursday. 4/7/23All Structural drawings are missing, please include structural drawings.