HomeMy WebLinkAbout291747_4_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101111683-84
PROJECT ADDRESS:
1017 S Fairview St
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
A-2
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
8/18/2022
INITIAL REVIEW
8/21/2022
EXPIRATION
2/14/2023
RECHECKS:
1.11/14/2022
PROJECT APPLICANT CONTACT PERSON:
2.3/8/2023
Alfredo Rodriguez
3.
TEL:
(909)374-2597
FAX:
VALUATION: $200,000.00
EMAIL:
aedengineering@yahoo.com
FLOOD ZONE: X-0602320256J
APPLICABLE CODE: 2019 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Fire Department approval on the corrected/final sets of drawings ((714)573-6100)
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)
- County of Orange Health Department approval on the corrected/final set of drawings ((714)433-6000)Assembly (A) occupancy: Plans shall be stamped, signed and dated by a California registered civil engineer or a California licensed architect. Sheet A-1: Provide building code analysisjustifying floor area(s) of building(s) (CBC Sections 503, 506, 507, and 508 and CBC Table 506.2)2nd Review Comment: The assembly area (restaurant) and occupant loads have been increased . Please provide area analysis to show compliance with the building allowable area. 3rd Review Comment: Allowable area analysis provided on sheet A-6 was incorrect. Please Provide calculation to show compliance with Section 508.4.1 for separated occupancies in a same building. Please see mark-up plan for additional information. Occupancies separation may be required per Table 508.4. 2nd Review Comment: Response was incomplete. Please revised floor plan to clearly show 2-hour fire-rated wall; revise wall line and wall legend. The two layers of 5/8” type ‘X’ gypsum boards are required on both sides of wall. Please revise wall assembly details and provide section elevation to show wall termination at roof sheathing. Details shall be clearly cross-referenced onto the plan. 3rd Review Comment: Fire barrier wall shall be rated for both sides of wall. Detail E/A-4 and SectionB/A-5 did not match with the UL U336 wall assembly. Please provide detail to show complete assembly construction of wall, including insulation, ¾” air space, steel stud, etc. Revise detail and wall sections. The two layers of type ‘x’ gypsum board shall extended to the roof sheathing. (End Comments)