HomeMy WebLinkAbout300388_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101114495
PROJECT ADDRESS:
1618 W First St
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
V B
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
4/3/2023
INITIAL REVIEW
4/9/2023
EXPIRATION
9/30/2023
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Joven Lactaoen
3.
TEL:
(323)304-3275
FAX:
VALUATION: $60,000.00
EMAIL:
Jovensinc@gmail.com
FLOOD ZONE: X-0602320257J
APPLICABLE CODE: 2022 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)Sheet A1: Sheet Index: MEP – Please specify “Under Separate Review”.Sheet A2: On the plan, please provide an accessible route from the public sidewalk to the primary accessible entrance. Accessible route shall be 5% slope maximum, measured in the direction of travel, and 2% maximum cross-slope. Accessible path of travel that exceeding 5% slope shall be designed as ramp in accordance with Section 11B-405. Sheet A4 & A5: On the plan, please clarify the areas/spaces located on the right side of the improved area are occupied with same tenant or separate tenants. If the area located to the right of the T.I space is a common use area, please provide the following:Specify Common HallwayCommon restroomsSpecify doors 4 & door 1 shall not be locked and shall be readily openable from the egress side without the use of a key or special knowledge or effort.If there are multiple tenant spaces (suites), please clearly identify/label demising walls and suite number on the plan. Door to facial and waxing rooms: Please show/provide minimum 18” clear from door strike edge and 60” clear door landing on the pull side and 48” on the push side. Accessible toilet compartments – please show dimension of 60” clear compartment and water closet located at 17”-18” from the adjacent wall. Exterior doors: Please show minimum 60” door landing and maneuver space. Provide the following notes on the plan:
Egress doors/gates shall be readily openable from the egress side without the use of a key or special knowledge or effort. (1010.1.9)
Openable parts of such hardware shall be 34 inches minimum and 44 inches maximum above the finish floor or ground.
The force for pushing or pulling open a door shall be 5-lb maximum.
Operable parts shall be operable with one hand and shall not require tight grasping, pinching, or twisting of the wrist.
A readily visible durable sign posted on the egress side on or adjacent to the main exit door stating: “THIS DOOR TO REMAIN UNLOCKED WHEN THIS SPACE IS OCCUPIED”, is required. (1010.1.9.4)(End of Comment)