HomeMy WebLinkAbout301974_2_Corrections.docxRESIDENTIAL PLAN CHECK COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101115027 PROJECT ADDRESS: 725 S Parton St PLAN CHECK ENGINEER: Huang, GaryTEL:714 647-5862 EMAIL: Ghuang@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: V B OCCUPANCY CLASSIFICATION(S): R-3 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 5/10/2023 INITIAL REVIEW 5/18/2023 EXPIRATION 11/6/2023 RECHECKS: 1. PROJECT APPLICANT CONTACT PERSON: 2. Pam McCaskey 3. TEL: (714)305-0772 FAX: VALUATION: $8,750.00 EMAIL: pam@saberemail.com FLOOD ZONE: X-0602320276J GUIDELINES: Comments contained within this report reflect only those of the Building and Safety Division. Additional comments or corrective action may be required by other Departments and/or outside Agencies This Plan Review Report and all subsequent code references are based upon the most recent version(s) of the 2022 California Building Codes (CBC, CRC, CFC, CEC, CPC, CMC, CGBSC, and CEES) The approval of plans and any supporting documents does not permit the violation of any section of the adopted building codes or other pertinent local ordinances, or state and federal laws All listed plan review comments must be adequately addressed before a building permit can be issued Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used. PLAN REVIEW COMMENTS: Applicant shall address all the checked‘☒’ correction comments below before resubmitting plans to Building Safety for recheck. ☒1. The applicant shall obtain clearances/approvals for the following, prior to building permit issuance: ☒Planning Division approval on the corrected/final set of drawings (647-5804). Previously approved plans should be submitted to expedite the process. ☐Fire Department approval on the corrected/final set of drawings (647-5839 or 647-5700). ☐Police Department approval on the corrected/final set of drawings (647-5840). ☐Public Works Agency approval (647-5039). ☐Proof of Worker's Compensation Insurance shall be required at the time of permit issuance. ☐School District Approval; and a copy of the school fee worksheet, completed by the plan check engineer, shall be required by the School District to verify the scope of the work. ☐Grading Permit. Application is made through the Building Safety Division (647-5800) and the plan review is by the Public Works Agency (647-5039). Sheet S1.0 Engineer to reference/identify on plan which anchorage option to be used Engineer to provide calculation to justify side plate’s adequacy to transfer lateral loads from sill plate to foundation Sheet SD1.0 Anchorage for side plate on trapezoidal footing: Engineer to specify post-install expansion anchor’s manufacture and size used Anchorage for side plate on footing: Engineer to verify/clarify, for post-installation, should it be threaded rod? ALT Anchorage for side plate on footing: Engineer to provide calculation to justify ½” diameter lag screw at 6’0” on center is adequate to transfer required shear. Red marked comment set is available to pick-up at the City Hall.(End of Comment)