Loading...
HomeMy WebLinkAbout296981_7_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101113395 PROJECT ADDRESS: 3201 S Halladay St PLAN CHECK ENGINEER: Le, TungTEL:714 647-5896 EMAIL: Tle10@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: III-B OCCUPANCY CLASSIFICATION(S): B, S-1 PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 1/24/2023 **Changed of designer at the 5th submittal INITIAL REVIEW 1/29/2023 EXPIRATION 7/23/2023 RECHECKS: 1.4/16/23 PROJECT APPLICANT CONTACT PERSON: 2.5/30/23 Dave Gamboa Tera Wray 3.6/30/23 4. 8/1/23 5. 8/28/23 6. 9/8/23 TEL: (707)889-4659 FAX: VALUATION: $100,000.00 EMAIL: tera@tomchou.com FLOOD ZONE: X-0602320278J APPLICABLE CODE: 2022 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Fire Department approval on the corrected/final sets of drawings ((714)573-6100) - Police Department approval on the corrected/final set of drawings (647-5840) - Public Works Agency approval (647-5039)*Additional plan check fee (5 hours)is be required due to plan check comments have not been addressed/resolved. A meeting with the engineer of record may be required.Review CommentsPlan was incomplete. Architectural plans were not provided/included with the resubmittal. Please provide three (3) complete sets of plans for review and approval. Plan was incomplete. Please provide complete architectural plans. Plan recheck will not be proceeded if incomplete set of plans are provided. Sheet S2: new footings adjacent to the existing wall – Please reference to detail 3/S2 (similar) for the column & new footing construction. Plan was not revised. Please comply. Sheet S2: new footing detail reference 3/S2 – please specify (typical) on the foundation plan. Plan was not revised. Please comply. Sheet SW-2: Detail 9, 12, 13 – Please specify spacing of the diagonal bracings. (End of Comments)