HomeMy WebLinkAbout305617_2_Corrections.docxTENANT IMPROVEMENT PLAN CHECK COMMENTS COMMENTS Planning & Building Agency Building Safety Division 20 Civic Center Plaza P.O. Box 1988 (M-19) Santa Ana, CA 92702 (714) 647-5800 www.santa-ana.org PLAN CHECK NO: 101116182 PROJECT ADDRESS: 1931 N Tustin Ave PLAN CHECK ENGINEER: Le, TungTEL:714 647-5896 EMAIL: Tle10@santa-ana.orgFAX:714 647-5897 TYPE OF CONSTRUCTION: III B OCCUPANCY CLASSIFICATION(S): B PLAN CHECK DATES: REMARKS/RECHECK ITEMS: APPLICATION 8/10/2023 INITIAL REVIEW 8/19/2023 EXPIRATION 2/6/2024 RECHECKS: 1.10/7/23 PROJECT APPLICANT CONTACT PERSON: 2. Mark Dimitroff 3. TEL: (949)226-9517 FAX: VALUATION: $28,000.00 EMAIL: mjd.troff@yahoo.com FLOOD ZONE: X-0602320164J APPLICABLE CODE: 2022 CALIFORNIA BUILDING CODE (CBC) WITH CITY OF SANTA ANA AMENDMENTS All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.The applicant shall obtain clearances/approvals for the following prior to building permit issuance: - Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans should be submitted to expedite the process. - Police Department approval on the corrected/final set of drawings (647-5840) - Public Works Agency approval (647-5039)Sheet CS-1: Occupancy Group: If the intend use of the space is for training/teaching and skill development, not in a school or academic program and not classified as assembly use, it may classify as group ‘B’ occupancy. (304.1)2nd Review Comment:On the plan, please specify the maximum occupant loads of the building. Sheet IN-1 & SPE-1: Location of accessible parking access aisle in relative to the entrance door: A minimum 5-ft landing and maneuver space is required at the door, and a minimum 3-ft strip of truncated dome shall be provided outside the required maneuver space. 2nd Review Comment: Please revise plan to extend the truncated dome on the hinged side of door (see marked-up plan). The accessible parking and access aisle should ship away from the maneuver space and truncated dome (5-ft landing + 3-ft truncated dome strip). 2nd Review Comment: Van accessible parking shall be minimum of 12-ft wide with 5-ft access ailse. Please coordinate and revise plans as required above.