HomeMy WebLinkAbout296981_8_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101113395
PROJECT ADDRESS:
3201 S Halladay St
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
III-B
OCCUPANCY CLASSIFICATION(S):
B, S-1
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
1/24/2023
**Changed of designer at the 5th submittal
INITIAL REVIEW
1/29/2023
EXPIRATION
7/23/2023
RECHECKS:
1.4/16/23
PROJECT APPLICANT CONTACT PERSON:
2.5/30/23
Dave Gamboa Tera Wray
3.6/30/23
4. 8/1/23
5. 8/28/23
6. 9/8/23
7. 10/16/23
TEL:
(707)889-4659
FAX:
VALUATION: $100,000.00
EMAIL:
tera@tomchou.com
FLOOD ZONE: X-0602320278J
APPLICABLE CODE: 2022 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 3corrected sets of plans.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Fire Department approval on the corrected/final sets of drawings ((714)573-6100)
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)*Additional plan check fee (5 hours)is be required due to plan check comments have not been addressed/resolved. A meeting with the engineer of record may be required.Review CommentsPlan was incomplete. Architectural plans were not provided/included with the resubmittal. Please provide three (3) complete sets of plans for review and approval. Plan was incomplete. Please provide complete architectural plans. Plan recheck will not be proceeded if incomplete set of plans are provided. Please resolve the following outstanding comments:Plan Sheet SW-1: Proposed First Floor: Detail 5/SW-2 called out on the First Floor was not applicable. Please omit/delete detail 5/SW-2 callout on the plan.Plans reference to detail 7/SW-2 but detail 7/SW-2 was not provided on sheet SW-2. Please clearly show/provide detail 7 on sheet SW-2. Second Floor Plan: Please do not show floor joist information and refer to structural framing plan for the structural information. Sheet SW-1 & SW-2 shall be signed and dated by the engineer of record. Structural plans for the proposed Second Floor metal deckSheet S3 was not provided (missing). Please include sheet S3 for the Deck Framing Plan. (End of Comments)