HomeMy WebLinkAbout305617_3_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101116182
PROJECT ADDRESS:
1931 N Tustin Ave
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
III B
OCCUPANCY CLASSIFICATION(S):
B
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
8/10/2023
INITIAL REVIEW
8/19/2023
EXPIRATION
2/6/2024
RECHECKS:
1.10/7/23
PROJECT APPLICANT CONTACT PERSON:
2.
Mark Dimitroff
3.
TEL:
(949)226-9517
FAX:
VALUATION: $28,000.00
EMAIL:
mjd.troff@yahoo.com
FLOOD ZONE: X-0602320164J
APPLICABLE CODE: 2022 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)Sheet CS-1: Occupancy Group: If the intend use of the space is for training/teaching and skill development, not in a school or academic program and not classified as assembly use, it may classify as group ‘B’ occupancy. (304.1)2nd Review Comment:On the plan, please specify the maximum occupant loads of the building. Sheet IN-1 & SPE-1: Location of accessible parking access aisle in relative to the entrance door: A minimum 5-ft landing and maneuver space is required at the door, and a minimum 3-ft strip of truncated dome shall be provided outside the required maneuver space. 2nd Review Comment: Please revise plan to extend the truncated dome on the hinged side of door (see marked-up plan). The accessible parking and access aisle should ship away from the maneuver space and truncated dome (5-ft landing + 3-ft truncated dome strip). 2nd Review Comment: Van accessible parking shall be minimum of 12-ft wide with 5-ft access ailse. Please coordinate and revise plans as required above.