HomeMy WebLinkAbout309900_1_Corrections.docxTENANT IMPROVEMENT
PLAN CHECK COMMENTS
COMMENTS
Planning & Building Agency
Building Safety Division
20 Civic Center Plaza
P.O. Box 1988 (M-19)
Santa Ana, CA 92702
(714) 647-5800
www.santa-ana.org
PLAN CHECK NO:
101117469
PROJECT ADDRESS:
3535 W Garry Ave
PLAN CHECK ENGINEER:
Le, TungTEL:714
647-5896
EMAIL:
Tle10@santa-ana.orgFAX:714
647-5897
TYPE OF CONSTRUCTION:
III B, SPK
OCCUPANCY CLASSIFICATION(S):
F-1, S-1, S-2
PLAN CHECK DATES:
REMARKS/RECHECK ITEMS:
APPLICATION
11/17/2023
INITIAL REVIEW
11/28/2023
EXPIRATION
5/15/2024
RECHECKS:
1.
PROJECT APPLICANT CONTACT PERSON:
2.
Brad Kenson
3.
TEL:
(949)228-5687
FAX:
VALUATION: $10,000.00
EMAIL:
brad@fastrackpower.com
FLOOD ZONE: X-0602320258J
APPLICABLE CODE: 2022 CALIFORNIA BUILDING CODE (CBC) WITH
CITY OF SANTA ANA AMENDMENTS
All items noted on this plan check report must be addressed. If you feel that an item is not applicable to your project, note “N/A” and discuss the reason with the plan checker.Please indicate the sheet number and detail to the right of each correction, or note the number on the plans where the correction is made. Resubmit marked original, calculations and this correction sheet. A separate sheet for response may be used.Resubmit 2corrected sets of plans.The applicant shall obtain clearances/approvals for the following prior to building permit issuance:
- Planning Division approval on the corrected/final set of drawings (647-5804.) Previously approved plans
should be submitted to expedite the process.
- Fire Department approval on the corrected/final sets of drawings ((714)573-6100)
- Police Department approval on the corrected/final set of drawings (647-5840)
- Public Works Agency approval (647-5039)Sheet ST1.1: Landscape plants provided on the accessible ramp adjacent to building wall (between the transformer) – Please remove plants from the ramp. New 3-ft wide pedestrian gate: Please provide detail for gate to show minimum 10” smooth surface on the push side and panic hardware, and level landing on both sides of gate/door. For clarity, please provide detail of new steel bollards. New roof-top screen: Please provide structural details and calculation for the proposed roof screen. (End of Comment)